BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M335396
Premises: 436 WEST BROADWAY MANHATTAN BIN: 1007733     Block: 502   Lot: 23
   
Application Completed and Certified

Filed: 438 W BROADWAY Census Tract:   49 Health Area:  6800
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   SPRING STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 03/06/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/03/2013 10:18 AM
Application Entered:   01/03/2013 Job Start Date:   01/03/2013
Last Change:   03/06/2013 Job End Date:   01/10/2013
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     02/20/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012417 Licensee Name: GABRIEL DUMITRU
Firm: 004208 Firm Name: ESSEX ELECTRIC INC
Firm Phone: 347-531-0801  Firm Address: 38-14 BROADWAY ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $111.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 10 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TED PRONEO
Owner Business Name: AESOP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  20 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  GND  30  15    41         
Buildings Total 30  15    41              
Total Units : 97 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/24/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M335396
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/17/2013 01/24/2013 JVA A (50) (4) Y
INSPECTION COMMENTS: CONDENSER UNIT IS ON ROOF
 
(2) 02/20/2013 02/28/2013 LBI C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M335396
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GBD FLR 220V CONDENSATE PUMP AND GFI ON ROOF ON SAME CKT (210.4C
RSLV 01/17/2013 01/17/2013 02/20/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF AC DTS SW NOT PROPERLY GRDED (EGC'S SPLRAD)(250.112)
RSLV 01/17/2013 01/17/2013 02/20/2013
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT 12X12 BOX FOR RISER NOT PROPERLY COVERED (314.25)
RSLV 01/17/2013 01/17/2013 02/20/2013
 
004 ( 30) OUTLET BOXES ARE NOT SECURED
BSMT 12X12 BOX FOR RISER NOT PROPERLY SECURED (314.23)
RSLV 01/17/2013 01/17/2013 02/20/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.