BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M335202
Premises: 1125 MADISON AVENUE MANHATTAN BIN: 1046820     Block: 1496   Lot: 21
   
Application Completed and Certified

Filed: 1127 MADISON AV Census Tract:   150.01 Health Area:  3600
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
Special Place Name:   NEWORK, NY
DOB Cross Street(s):   EAST 84 STREET,    EAST 85 STREET
Status:   C - JOB IS SIGNED OFF 07/10/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/21/2012 8:27 PM
Application Entered:   12/21/2012 Job Start Date:   12/24/2012
Last Change:   07/10/2013 Job End Date:   06/30/2013
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     07/01/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010809 Licensee Name: JOHN L RICKFORD
Firm: 002075 Firm Name: R.J.ELECTRICAL CONTRACTOR
Firm Phone: 718-949-5466  Firm Address: 201-11 LINDEN BLVD ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $59.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   BEAUTY SALON
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOANNE LEE
Owner Business Name: MADISON AVE BEAUTY SALON
Authorized Representative:  RICKFORD JOHN
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  SALON  40  36  10               
Buildings Total 40  36  10                  
Total Units : 88 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/05/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING BEAUTY SALON ON FIRST FLOOR FOR RECEPTACLES, FIXTURES AND SWITCHES. NO OTHER WORK DONE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M335202
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/26/2013 03/11/2013 TSO N (15) (0) Y
INSPECTION COMMENTS: *NO SHOW*
 
(2) 03/14/2013 03/23/2013 TSO A (40) (4) Y
INSPECTION COMMENTS: X
 
(3) 03/27/2013 04/05/2013 EDB A Y (65) (7) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(4) 05/16/2013 05/24/2013 JKF Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(5) 07/01/2013 07/10/2013 LBI C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M335202
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL MULTI WIRE BRANCH CIRCUITS NEED HANDLE TIME 210.4
RSLV 03/14/2013 03/14/2013 03/27/2013
 
002 (999) OTHER
FLEXIBLE CORD RUN THROUGH WALL (LED) 400.8
RSLV 03/14/2013 03/14/2013 03/27/2013
 
003 (999) OTHER
MULTIWIRE BRANCH CIRCUIT RECEPTACLE CANNOT BREAK NEUTAL
RSLV 03/14/2013 03/14/2013 03/27/2013
 
004 (999) OTHER
PANEL NOT RATED FOR TWO BREAKERS 110.3
RSLV 03/14/2013 03/14/2013 03/27/2013
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
1FL: G.F.C.I.WITHIN 6' FROM SINK NOT PROVIDED.... - 210.8
RSLV 03/27/2013 03/27/2013 07/01/2013
 
006 (252) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
1FL: LINE AND LOW VOLTAGE IN SAME RACEWAY(RECEPT.ON)... - 725
RSLV 03/27/2013 03/27/2013 07/01/2013
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
1FL: INSIDE CABINET OPEN BOX BY MIRROR.... - 314.25
RSLV 03/27/2013 03/27/2013 07/01/2013
 
008 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
1FL: INSIDE CABINET BY MIRROR WALL AC LABEL NOT PROPERLY TERMINATED- 320.40
RSLV 03/27/2013 03/27/2013 07/01/2013
 
009 ( 29) OUTLET BOXES ARE NOT COVERED
1FL: RECEPTION AREA LB NOT COVERED...... - 314.25
RSLV 03/27/2013 03/27/2013 07/01/2013
 
010 (135) DEFECTIVE GROUND ROD IS IN USE
1FL: RECEPTION AREA RECEPTACLE NO EQUIPMENT GND.... - 250.48
RSLV 03/27/2013 03/27/2013 07/01/2013
 
011 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
1FL: RECEPTION AREA AC CABLE NOT PROPERLY TERMINATED... - 320.40
RSLV 03/27/2013 03/27/2013 07/01/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.