| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER PANEL MULTI WIRE BRANCH CIRCUITS NEED HANDLE TIME 210.4 |
RSLV |
03/14/2013 |
03/14/2013 |
03/27/2013 |
| |
| 002 |
(999) |
OTHER FLEXIBLE CORD RUN THROUGH WALL (LED) 400.8 |
RSLV |
03/14/2013 |
03/14/2013 |
03/27/2013 |
| |
| 003 |
(999) |
OTHER MULTIWIRE BRANCH CIRCUIT RECEPTACLE CANNOT BREAK NEUTAL |
RSLV |
03/14/2013 |
03/14/2013 |
03/27/2013 |
| |
| 004 |
(999) |
OTHER PANEL NOT RATED FOR TWO BREAKERS 110.3 |
RSLV |
03/14/2013 |
03/14/2013 |
03/27/2013 |
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1FL: G.F.C.I.WITHIN 6' FROM SINK NOT PROVIDED.... - 210.8 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |
| |
| 006 |
(252) |
LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE 1FL: LINE AND LOW VOLTAGE IN SAME RACEWAY(RECEPT.ON)... - 725 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |
| |
| 007 |
( 29) |
OUTLET BOXES ARE NOT COVERED 1FL: INSIDE CABINET OPEN BOX BY MIRROR.... - 314.25 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |
| |
| 008 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED 1FL: INSIDE CABINET BY MIRROR WALL AC LABEL NOT PROPERLY TERMINATED- 320.40 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |
| |
| 009 |
( 29) |
OUTLET BOXES ARE NOT COVERED 1FL: RECEPTION AREA LB NOT COVERED...... - 314.25 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |
| |
| 010 |
(135) |
DEFECTIVE GROUND ROD IS IN USE 1FL: RECEPTION AREA RECEPTACLE NO EQUIPMENT GND.... - 250.48 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |
| |
| 011 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED 1FL: RECEPTION AREA AC CABLE NOT PROPERLY TERMINATED... - 320.40 |
RSLV |
03/27/2013 |
03/27/2013 |
07/01/2013 |