BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M335185
Premises: 85 SOUTH STREET MANHATTAN BIN: 1001142     Block: 72   Lot: 27
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 85 SOUTH ST Census Tract:   15.02 Health Area:  7700
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   FLETCHER STREET,    JOHN STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/21/2012 12:16 PM
Application Entered:   12/21/2012 Job Start Date:   12/21/2012
Last Change:   08/22/2025 Job End Date:   03/05/2013
Appointment Status:   
Last Inspection By:   ROGALEWSKI, M       On     05/29/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 009165 Licensee Name: CARMINE J CAMENZULI
Firm: 003589 Firm Name: JLC ELEC'L CONTR'G INC
Firm Phone: 718-932-2499  Firm Address: 14-45 BROADWAY LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $0.00
Hurricane Sandy Damage:   Yes
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARIN MABEL
Owner Business Name: 83-85 WITH STREET PLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 4 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 12/21/2012 Notice: 1 - FIRST NOTICE 05/30/2013
Power Issued: 12/21/2012 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M335185
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/29/2013 05/30/2013 MIR A G (60) (6) Y
INSPECTION COMMENTS: **SEE OBJECTIONS

OBJECTION FOR APPLICATION #: M335185
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: NEUTRAL NOT BONDED BOTH SERVOCE SWITCHES
OPEN 05/29/2013 05/29/2013
 
002 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
BSMT: SERVICE WATER GROUND RACEWAY
OPEN 05/29/2013 05/29/2013
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT: L.B COVERS MISSING...1 1/2 - 4"
OPEN 05/29/2013 05/29/2013
 
004 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
BSMT: WHITE WIRE USED FOR GRD AND WATER GRD
OPEN 05/29/2013 05/29/2013
 
005 ( 23) PORTABLE EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT: GRD ROD WIRE S/S NO CONNECTOR
OPEN 05/29/2013 05/29/2013
 
006 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
BSMT: SPLIT BOLT USED FOR TAP OF FEEDERS
OPEN 05/29/2013 05/29/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back