Electrical Application Details for App #: M335181
Premises: 30 CARMINE STREET MANHATTAN BIN: 1008364     Block: 527   Lot: 68
   
Application Completed and Certified

Filed: 30 CARMINE ST Census Tract:   67 Health Area:  6400
CELLARTO FOURTH FLOOR, ROOF Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   BLEECKER STREET,    BEDFORD STREET
Status:   C - JOB IS SIGNED OFF 10/21/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/21/2012 10:58 AM
Application Entered:   12/21/2012 Job Start Date:   12/21/2012
Last Change:   10/21/2013 Job End Date:   11/23/2014
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     08/19/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009639 Licensee Name: THOMAS S CARNEY
Firm: 003614 Firm Name: ROYAL ELEC'L & WIRING COR
Firm Phone: 718-584-1424  Firm Address: 2558 MARION AVENUE 1 BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $786.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 9 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: C&R CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1#600A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  9#3/3 BX
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1#3/O THHN
D. Over 250 MCM  2  2#350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  10#20 BREAKERS 220V 100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1#100A 3 PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  CELL                 
GND  APT A  20  32  12               
MZ1  AP 1B  15  30               
MZ1  AP.1A  14  26               
MZ2  AP 2A  14  26               
MZ3  AP.3A  14  26               
MZ3  AP.3B  15  30               
MZ4  AP.4A  14  26               
MZ4  AP4B  15  30               
Buildings Total 127  231  28  68                  
Total Units : 454 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 9 #4-Wire 2 #10-Wire 0
Existing Meters 10 + New Meters 11 - Removed Meters 10 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/21/2012 Notice: 1 - FIRST NOTICE 07/27/2013
Power Issued: 12/21/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M335181
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/26/2013 07/02/2013 IOS A G (80) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 07/18/2013 07/27/2013 GYM A R E (60) (3) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(3) 08/19/2013 08/21/2013 LBI C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M335181
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GROUND NOT WITHIN 5 FEET FROM BUILDING ENTRANCE
RSLV 06/26/2013 06/26/2013 07/18/2013
 
002 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
DEFECTIVE LIGHTING BY WATER MAIN
RSLV 06/26/2013 06/26/2013 07/18/2013
 
003 (999) OTHER
SEAL TIGHT NOT STRAPED FEEDING SPLIT UNIT ON FIRST FLOOR DECK 350.30
RSLV 06/26/2013 06/26/2013 07/18/2013
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PLP NOT LABELED
RSLV 06/26/2013 06/26/2013 07/18/2013
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
1/2 LB NOT COVERED NEXT TO PLP
RSLV 06/26/2013 06/26/2013 07/18/2013
 
006 (999) OTHER
MULTI CIRCUIT WIRE MOTOR 2 POLE BREAKER IN PLP 210.4(B)
RSLV 06/26/2013 06/26/2013 07/18/2013
 
007 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
14 AWG USED IN JUNCTION BOX FEEDING LIGHT FIXTURE BY WATER MAIN
RSLV 06/26/2013 06/26/2013 07/18/2013
 
008 (999) OTHER
ALL FLS: 40 AMP EKECTRIC OVEN/STOVES NEUTRAL BONDED ATER SERVICE SW- 250.24(APTS)
RSLV 07/18/2013 07/18/2013 08/19/2013
 
009 (999) OTHER
KITCHEN: OVEN OCP TOO LARGE..... - 310.16
RSLV 07/18/2013 07/18/2013 08/19/2013
 
010 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: COUNTER RECEPTACLES NOT WORKING
RSLV 07/18/2013 07/18/2013 08/19/2013