| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
1#600A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
9 |
9#3/3 BX |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1#3/O THHN |
| D. Over 250 MCM |
2 |
2#350 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
10 |
10#20 BREAKERS 220V 100A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
1#100A 3 PHASE |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY WATER GROUND NOT WITHIN 5 FEET FROM BUILDING ENTRANCE |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 002 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE DEFECTIVE LIGHTING BY WATER MAIN |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 003 |
(999) |
OTHER SEAL TIGHT NOT STRAPED FEEDING SPLIT UNIT ON FIRST FLOOR DECK 350.30 |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 004 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY PLP NOT LABELED |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 005 |
( 29) |
OUTLET BOXES ARE NOT COVERED 1/2 LB NOT COVERED NEXT TO PLP |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 006 |
(999) |
OTHER MULTI CIRCUIT WIRE MOTOR 2 POLE BREAKER IN PLP 210.4(B) |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 007 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE 14 AWG USED IN JUNCTION BOX FEEDING LIGHT FIXTURE BY WATER MAIN |
RSLV |
06/26/2013 |
06/26/2013 |
07/18/2013 |
| |
| 008 |
(999) |
OTHER ALL FLS: 40 AMP EKECTRIC OVEN/STOVES NEUTRAL BONDED ATER SERVICE SW- 250.24(APTS) |
RSLV |
07/18/2013 |
07/18/2013 |
08/19/2013 |
| |
| 009 |
(999) |
OTHER KITCHEN: OVEN OCP TOO LARGE..... - 310.16 |
RSLV |
07/18/2013 |
07/18/2013 |
08/19/2013 |
| |
| 010 |
( 19) |
DEFECTIVE WIRING IS IN USE KITCHEN: COUNTER RECEPTACLES NOT WORKING |
RSLV |
07/18/2013 |
07/18/2013 |
08/19/2013 |