NYC Department of Buildings
Electrical Application Details for App #: M334655
Premises: 565 BROADWAY MANHATTAN BIN: 1007573     Block: 498   Lot: 5
   
Application Completed and Certified

Filed: 565 BROADWAY Census Tract:   49 Health Area:  6800
3RD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   SPRING STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 06/26/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/05/2012 6:21 PM
Application Entered:   12/05/2012 Job Start Date:   12/06/2012
Last Change:   06/26/2014 Job End Date:   12/06/2013
Appointment Status:   
Last Inspection By:   BEST, J       On     06/18/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012208 Licensee Name: JAROSLAW JAROCKI
Firm: 003924 Firm Name: ADA ELECTRIC CORP
Firm Phone: 718-497-5750  Firm Address: 234 CHESTNUT STREET BROOKLYN NY 11208 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $265.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANDREW BROWN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3 FL  86  78    24    22         
Buildings Total 86  78    24       22           
Total Units : 210 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 0 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/05/2012 Notice: 1 - FIRST NOTICE 06/10/2014
Power Issued: 12/05/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M334655
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/02/2014 06/10/2014 EDB A E (60) (10) Y
INSPECTION COMMENTS: NONE
 
(2) 06/18/2014 06/26/2014 JSB C R E (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M334655
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
T-OUT MC CABLE NOT PROPERLY TERMINATED AT RECETIONL 330.40
RSLV 06/02/2014 06/02/2014 06/18/2014
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
T-OUT WOOD MOLD:RECEPTICAL NOT FLUSH W/WOOD 314.20,21
RSLV 06/02/2014 06/02/2014 06/18/2014
 
003 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
PANEL MAIN: NEUTRAL BONDED AFTER SERVICE: SW 250.24 A5
RSLV 06/02/2014 06/02/2014 06/18/2014
 
004 ( 17) DEFECTIVE SWITCHES ARE IN USE
PANEL SUBL DEFFECTIVE AFC5 CB IN USED AM. 110.2A
RSLV 06/02/2014 06/02/2014 06/18/2014
 
005 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
RAISER BSMT TO 3RD FE: EMT NOT SUPPORTED 358.30
RSLV 06/02/2014 06/02/2014 06/18/2014
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
A/C UNIT(S) ALL DISC. SW: EQUIPMENT GND NOT PROPERLY TEMINATED250..112 110.2
RSLV 06/02/2014 06/02/2014 06/18/2014
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
A/C UNITS ALL DISC SW: ZIP SCREW USED FOR GND 250.8 A5
RSLV 06/02/2014 06/02/2014 06/18/2014
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
KITCHEN LIGHT FIXTURE NOT APROVED 110.2
RSLV 06/02/2014 06/02/2014 06/18/2014
 
009 ( 19) DEFECTIVE WIRING IS IN USE
CELLING BY MASTER BED: OPEN WIRING AM 110.2Q
RSLV 06/02/2014 06/02/2014 06/18/2014
 
010 ( 29) OUTLET BOXES ARE NOT COVERED
CELLING BY MASTER BED: OUTLET BOX NOT COVERED 314.25
RSLV 06/02/2014 06/02/2014 06/18/2014