| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED T-OUT MC CABLE NOT PROPERLY TERMINATED AT RECETIONL 330.40 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 002 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED T-OUT WOOD MOLD:RECEPTICAL NOT FLUSH W/WOOD 314.20,21 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 003 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH PANEL MAIN: NEUTRAL BONDED AFTER SERVICE: SW 250.24 A5 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 004 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE PANEL SUBL DEFFECTIVE AFC5 CB IN USED AM. 110.2A |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 005 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) RAISER BSMT TO 3RD FE: EMT NOT SUPPORTED 358.30 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED A/C UNIT(S) ALL DISC. SW: EQUIPMENT GND NOT PROPERLY TEMINATED250..112 110.2 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED A/C UNITS ALL DISC SW: ZIP SCREW USED FOR GND 250.8 A5 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 008 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED KITCHEN LIGHT FIXTURE NOT APROVED 110.2 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 009 |
( 19) |
DEFECTIVE WIRING IS IN USE CELLING BY MASTER BED: OPEN WIRING AM 110.2Q |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |
| |
| 010 |
( 29) |
OUTLET BOXES ARE NOT COVERED CELLING BY MASTER BED: OUTLET BOX NOT COVERED 314.25 |
RSLV |
06/02/2014 |
06/02/2014 |
06/18/2014 |