BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M332839
Premises: 332 EAST 9 STREET MANHATTAN BIN: 1006371     Block: 450   Lot: 20
   
Application Completed and Certified

Filed: 332 E 9 ST Census Tract:   38 Health Area:  6500
332 EAST 9TH STREET Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 03/19/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/07/2012 2:19 PM
Application Entered:   10/07/2012 Job Start Date:   10/15/2012
Last Change:   03/19/2014 Job End Date:   10/31/2012
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     12/17/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010207 Licensee Name: VINCENT H COLE
Firm: 001547 Firm Name: WOODSIDE ELECTRIC CORP.
Firm Phone: 718-409-5607  Firm Address: 1408 SEABURY AVENUE BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $71.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EMILY TABAK
Authorized Representative:  EMILY TABAK
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF      16                 
Buildings Total   16                    
Total Units : 17 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/23/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW PHOTOVOLTIC SYSTEM TO SUPPLEMENT P.L.P LOAD.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332839
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/19/2013 11/23/2013 LBI A (30) (5) Y
INSPECTION COMMENTS: AC MODULE/MICRO INVERTER SYSTEM.PLP SVC GROUND RE-WIRED
 
(2) 12/17/2013 12/18/2013 LBI C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M332839
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: GROUND ELECTRODE COND RACEWAY NOT CONTINUOUS PER 250.64E
RSLV 11/19/2013 11/19/2013 12/17/2013
 
002 (999) OTHER
BSMT: ONE LINE DOES NOT ACCURATELY REFLECT INSTALLATION. AM 690.1
RSLV 11/19/2013 11/19/2013 12/17/2013
 
003 (999) OTHER
ROOF: PV LOAD CENTRE NOT LABELED PER 690.14C2
RSLV 11/19/2013 11/19/2013 12/17/2013
 
004 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
ROOF: IMC ON ROOF MISSING STRAPS. 342.30
RSLV 11/19/2013 11/19/2013 12/17/2013
 
005 (999) OTHER
ROOF: SPLICES IN J-BOX BETWEEN INVERTERS & AC DIS SW NOT WET RATED110.11,300.9
RSLV 11/19/2013 11/19/2013 12/17/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back