Electrical Application Details for App #: M332493
Premises: 12 EAST 11 STREET MANHATTAN BIN: 1009253     Block: 568   Lot: 9
   
Application Completed and Certified

Filed: 12 E 11 ST Census Tract:   61 Health Area:  5700
ENTIRE HOUSE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 06/23/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/28/2012 5:52 PM
Application Entered:   09/28/2012 Job Start Date:   09/28/2012
Last Change:   06/23/2015 Job End Date:   09/28/2013
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     06/04/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $713.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ATUL KHANNA
Owner Business Name: PROPERTY OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A (200A)
C. 201 Up to 600 AMPS  1  400 CTS(400LPJ-SP)
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  225A
D. 3 Phase Over 225 AMPS  1  400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL      20    14  40     
BAS      27    22  45         
001      27    22  45         
002      27    22  45  16     
003      27    22  45     
004      27    22  45     
ROF        24         
Buildings Total   157    125  267     33     41      
Total Units : 623 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 4 + New Meters 2 - Removed Meters 2 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/28/2012 Notice: C - CALL TO OFFICE 05/07/2015
Power Issued: 09/28/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332493
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/28/2015 05/07/2015 NRS A E (115) (10) Y
INSPECTION COMMENTS: ALSO HVAC WIRING AND FLOOR DESCRIPTION NOT ACCURATE
 
(2) 04/28/2015 05/07/2015 NRS A X E (115) (6) Y
INSPECTION COMMENTS: ALSO HVAC WIRING AND FLOOR DESCRIPTION
 
(3) 05/22/2015 05/29/2015 WYF N (30) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR,SAID HE CANCELED
 
(4) 06/04/2015 06/09/2015 TOR C R E (20) (0) Y
INSPECTION COMMENTS: OBJECTIONS INSPECTED ONLY

OBJECTION FOR APPLICATION #: M332493
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
CELLAR 400 CTS HAS BEEN MODIFIED: 400A.FUSES LOOSE, M.B.J DOES NOTFIT, WASHERS CHANGED, LUGS INSTALLED UNDER M.B.J
RSLV 04/28/2015 04/28/2015 06/04/2015
 
002 (999) OTHER
CELLAR LINESIDE BONDING NOT AS PER 250.66
RSLV 04/28/2015 04/28/2015 06/04/2015
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
CELLAR 400 ACTS REDUCING DONOUGHTS
RSLV 04/28/2015 04/28/2015 06/04/2015
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
CELLAR BOTH PANELS
RSLV 04/28/2015 04/28/2015 06/04/2015
 
005 (279) WATER METER JUMPER IS MISSING/IMPROPER
CELLAR WATER METER J. UNDERSIZED
RSLV 04/28/2015 04/28/2015 06/04/2015
 
006 (356) RACEWAY LACKS MECHANICAL CONTINUITY
CELLAR AIR HANDLER AND 1900 DISCONNECT
RSLV 04/28/2015 04/28/2015 06/04/2015
 
007 (999) OTHER
CELLAR A/H OCPD NOT AS PER SPECS 440.22 (C)
RSLV 04/28/2015 04/28/2015 06/04/2015
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT PENINSULA IN KITCHEN
RSLV 04/28/2015 04/28/2015 06/04/2015
 
009 (999) OTHER
BASEMENT KITCHEN: REC BOXES SET TOO DEEP IN COMBUTIBLE 344.20
RSLV 04/28/2015 04/28/2015 06/04/2015
 
010 (999) OTHER
1-2-3-4 OUTLETS IN COMBUSTIBLE SET TOO DEEP 314.20
RSLV 04/28/2015 04/28/2015 06/04/2015
 
011 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
2 FLOOR STUDY BAR RECE
RSLV 04/28/2015 04/28/2015 06/04/2015
 
012 (356) RACEWAY LACKS MECHANICAL CONTINUITY
2 FLOOR STEAM UNIT DISCONNECT: MC CABLE NOT IN CONNECTOR
RSLV 04/28/2015 04/28/2015 06/04/2015
 
013 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
3 FLOOR MAIN PANEL (PP3)
RSLV 04/28/2015 04/28/2015 06/04/2015
 
014 ( 53) GFCI HAS NOT BEEN PROVIDED
3 FLOOR KITCHEN QUAD COUNTER
RSLV 04/28/2015 04/28/2015 06/04/2015
 
015 (999) OTHER
3 FLOOR KITCHEN RECE BOXES SET TOO DEEP IN COMBUSTIBLE 314.20
RSLV 04/28/2015 04/28/2015 06/04/2015
 
016 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BASEMENT OUTSIDE FRONT UNDER STAIRS 1900 BOX SET SCREW EMT CONNECTOR
RSLV 04/28/2015 04/28/2015 06/04/2015