| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200A (200A) |
| C. 201 Up to 600 AMPS |
1 |
400 CTS(400LPJ-SP) |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
2 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
5 |
225A |
| D. 3 Phase Over 225 AMPS |
1 |
400A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED CELLAR 400 CTS HAS BEEN MODIFIED: 400A.FUSES LOOSE, M.B.J DOES NOTFIT, WASHERS CHANGED, LUGS INSTALLED UNDER M.B.J |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 002 |
(999) |
OTHER CELLAR LINESIDE BONDING NOT AS PER 250.66 |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 003 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED CELLAR 400 ACTS REDUCING DONOUGHTS |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED CELLAR BOTH PANELS |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 005 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER CELLAR WATER METER J. UNDERSIZED |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 006 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY CELLAR AIR HANDLER AND 1900 DISCONNECT |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 007 |
(999) |
OTHER CELLAR A/H OCPD NOT AS PER SPECS 440.22 (C) |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED BASEMENT PENINSULA IN KITCHEN |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 009 |
(999) |
OTHER BASEMENT KITCHEN: REC BOXES SET TOO DEEP IN COMBUTIBLE 344.20 |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 010 |
(999) |
OTHER 1-2-3-4 OUTLETS IN COMBUSTIBLE SET TOO DEEP 314.20 |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 011 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 2 FLOOR STUDY BAR RECE |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 012 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY 2 FLOOR STEAM UNIT DISCONNECT: MC CABLE NOT IN CONNECTOR |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 013 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 3 FLOOR MAIN PANEL (PP3) |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 014 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 3 FLOOR KITCHEN QUAD COUNTER |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 015 |
(999) |
OTHER 3 FLOOR KITCHEN RECE BOXES SET TOO DEEP IN COMBUSTIBLE 314.20 |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |
| |
| 016 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BASEMENT OUTSIDE FRONT UNDER STAIRS 1900 BOX SET SCREW EMT CONNECTOR |
RSLV |
04/28/2015 |
04/28/2015 |
06/04/2015 |