BIS Menu  |  Applications  |  Print Electrical Permit  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M332459
Premises: 95 VANDAM STREET MANHATTAN BIN: 1010376     Block: 597   Lot: 7501
   
Application Completed and Certified

Filed: 95 VAN DAM ST Census Tract:   37 Health Area:  6800
APT 3F Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   C - JOB IS SIGNED OFF 04/25/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/28/2012 8:01 AM
Application Entered:   09/28/2012 Job Start Date:   09/28/2012
Last Change:   04/25/2015 Job End Date:   09/28/2013
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     04/15/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009615 Licensee Name: ROBERT COVELLO
Firm: 001205 Firm Name: ROBERT S. COVELLO
Firm Phone: 718-786-7390  Firm Address: 51-20 35TH STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $184.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES MASELLA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3F  22  28    16  22             
Buildings Total 22  28    16  22                
Total Units : 88 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 7 + New Meters 1 - Removed Meters 1 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/28/2012 Notice: 1 - FIRST NOTICE 11/05/2014
Power Issued: 09/28/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332459
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/29/2014 11/05/2014 FRI A G (40) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 03/24/2015 03/31/2015 WYF Z (0) (0) Y
INSPECTION COMMENTS: CANCELED WITH OFFICE
 
(3) 04/15/2015 04/22/2015 WYF C R E (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M332459
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
KITCHEN: RECEPT NOT FLUSH W/ISLAND FURNITURE SURFACE. 110.12
RSLV 10/29/2014 10/29/2014 04/15/2015
 
002 (999) OTHER
C/B PNL: SHARED NEUTRAL CKTS - NEED C/B HANDLE TIE. 210.4B
RSLV 10/29/2014 10/29/2014 04/15/2015
 
003 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
ELEC.SVC: FUSES TO BE DERATED TO 175A
RSLV 10/29/2014 10/29/2014 04/15/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Print Electrical Permit  |  Electrical Inspection Work Order  |  Back