BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M332391
Premises: 215 WEST 40 STREET MANHATTAN BIN: 1024644     Block: 1012   Lot: 23
   
Application Completed and Certified

Filed: 215 W 40 ST Census Tract:   113 Health Area:  5200
1ST FL Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10018 Community Board:   105
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 12/04/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/26/2012 4:31 PM
Application Entered:   09/26/2012 Job Start Date:   09/26/2012
Last Change:   12/04/2014 Job End Date:   09/26/2013
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     10/28/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011393 Licensee Name: THOMAS J DOYLE
Firm: 003821 Firm Name: R3 ELECTRICAL, INC
Firm Phone: 718-370-2805  Firm Address: 541 PORT RICHMOND AVENUE STATEN ISLAND NY 10302 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $201.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 1 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: N/A N/A
Owner Business Name: 215 W. 40TH ST. BAR LLC
Authorized Representative:  RAY D'AURIA
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1 200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20  40    10  20         
Buildings Total 20  40    10  20              
Total Units : 96 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/02/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332391
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/24/2014 05/02/2014 IOS A (50) (6) Y
INSPECTION COMMENTS: NONE
 
(2) 06/02/2014 06/10/2014 DNM Z (0) (0) Y
INSPECTION COMMENTS: CANCELLED WITH OFFICE
 
(3) 07/01/2014 07/14/2014 NRS N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW. NO ANSWER
 
(4) 09/18/2014 09/24/2014 EID J Y (40) (0) Y
INSPECTION COMMENTS: CONT DBL UP ON NEUTRALS IN THROUGH TO PARALLEL MULTI CKT WIRE
 
(5) 10/03/2014 10/14/2014 EID N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW,SAID HE COULD NOT MAKE APPT
 
(6) 10/28/2014 10/30/2014 TOR C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M332391
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
CELLAR: TROUGH ABOVE PANEL IS NOT COVERED
RSLV 04/24/2014 04/24/2014 09/18/2014
 
002 ( 31) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX
CELLAR: TROUGH ABOVE PANEL IS OVER FILLED
RSLV 04/24/2014 04/24/2014 09/18/2014
 
003 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
CELLAR: WIRES IN 2" FMC IN PANEL NEED DERATING 39 CURRENT CARRYINGCONDUCTORS
RSLV 04/24/2014 09/18/2014 10/28/2014
 
004 (999) OTHER
CELLAR: CIRCUITS NOT GROUPED IN PANEL. 210.4
RSLV 04/24/2014 09/18/2014 10/28/2014
 
005 (999) OTHER
CELLAR: 2 WIRES UNDER ONE LUG IN 200A DISCONNECT. 110.14
RSLV 04/24/2014 04/24/2014 09/18/2014
 
006 (999) OTHER
1ST FLOOR: BOXES TOO DEEP IN WOOD PANELS. 314.20
RSLV 04/24/2014 09/18/2014 10/28/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back