| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
400 AMP |
| D. 601 Up to 1200 AMPS |
1 |
600 AP |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
SETS # 2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
7 |
SET 3/0 |
| D. Over 250 MCM |
8 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
7 |
40 CIRCUIT |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
HYDRO |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED BSMT: BRANCH CIRCUITS IN PLP TO BE DERATED AT 50%3/4 EMT HAS MORE THAN 10 CURRENT CARRYING CONDUCTORS |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 002 |
(999) |
OTHER BSMT-ROOF: HEATERS IN STAIRCASE HAVE NO DISCONNECT. 422.34 |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 003 |
(999) |
OTHER BSMT-ROOF: NO G.F.C.I.RECEPTACLE FOR ISLANDS IN KITCHENS. 210.52 |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 004 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION BSMT-ROOF: LOAD CALCULATIONS REQUIRED FOR PANELS |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED BSMT-ROOF: A.F.C.I.BREAKERS NOT PROVIDED THROUGH-OUT |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 006 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER BSMT-ROOF: NOT ALL FIXTURES IN BATHROOMS ARE VAPOR PROOF |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 007 |
(999) |
OTHER PENTHOUSE: NO G.F.C.I.RECEPTACLE WITHIN 6' OF SINK. 210.8 |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 008 |
(999) |
OTHER BSMT: NO FLANGE INSTALLED AT END OF TROUGH GOING INTO THE ENDLINEBOX. 376.100 |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 009 |
( 38) |
MOTOR OVERCURRENT DEVICE DOES NOT HAVE THE PROPER RATING BSMT: ELEVATOR DISCONNECT IS OVER FUSED MORE THAN 175%. 16.2FLA |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 010 |
(999) |
OTHER BSMT: NO G.E.C.FOR TRANSFORMER. 450.10 |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 011 |
(999) |
OTHER BSMT: SECODARY SIDE OF TRANSFORMER IS OVER FUSED. 240.21(C)(1) |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |
| |
| 012 |
(999) |
OTHER BSMT: PRIMARY SIDE OF TRANSFORMER IS OVER FUSED. 240.21(C)(1) |
RSLV |
03/27/2014 |
03/27/2014 |
04/17/2014 |