BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M332319
Premises: 37 GREAT JONES STREET MANHATTAN BIN: 1008478     Block: 530   Lot: 25
   
Application Completed and Certified

Filed: 37 GREAT JONES ST Census Tract:   55.02 Health Area:  5700
ENTIRE BUILDING Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   LAFAYETTE STREET,    BOWERY
Status:   C - JOB IS SIGNED OFF 05/02/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/25/2012 12:09 PM
Application Entered:   09/25/2012 Job Start Date:   09/25/2012
Last Change:   05/02/2014 Job End Date:   09/30/2013
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     04/17/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010851 Licensee Name: RONALD J TESTA, JR.
Firm: 001416 Firm Name: TESTA ELECTRIC CO., INC
Firm Phone: 718-331-2747  Firm Address: 1435 65TH STREET, 2ND FL BROOKLYN NY 11219 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
009514 TESTA, RONALD 001416 TESTA ELECTRIC CO., INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $2,041.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: GREAT JONES PROPERTIES LL
Authorized Representative:  ROGER DIB
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  400 AMP
D. 601 Up to 1200 AMPS  1  600 AP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  SETS # 2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  7  SET 3/0
D. Over 250 MCM  8  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  40 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  HYDRO
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BASE    20    10  50  25 
GND  STR      10         
001  APT 1    40    13  15         
002  APT 2    40    13  15     
003  APT 3    40    13  15         
004  APT 4    50    16  25     
ROF  ROOF      20         
Buildings Total   193    68  131     65       
Total Units : 474 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 5 #10-Wire 1
Existing Meters 6 + New Meters 6 - Removed Meters 6 = Total Meters 6

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/25/2012 Notice: 1 - FIRST NOTICE 04/05/2014
Power Issued: 09/25/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  COMPLETE WIRING FOR ENTIRE BUILDING. (4) APARTMENTS (1) COMMERCIAL SPACE. COMPLETE SERVICE. NEW RISERS AND PANELS. ALL HVAC, ELEVATOR AND FIRE ALARM SYSTEM.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332319
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/27/2014 04/05/2014 IOS V G (130) (12) Y
INSPECTION COMMENTS: TEMPORARY WIRING IS UP FOR STORE
 
(2) 04/17/2014 04/29/2014 DNM C R E (35) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: M332319
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
BSMT: BRANCH CIRCUITS IN PLP TO BE DERATED AT 50%3/4 EMT HAS MORE THAN 10 CURRENT CARRYING CONDUCTORS
RSLV 03/27/2014 03/27/2014 04/17/2014
 
002 (999) OTHER
BSMT-ROOF: HEATERS IN STAIRCASE HAVE NO DISCONNECT. 422.34
RSLV 03/27/2014 03/27/2014 04/17/2014
 
003 (999) OTHER
BSMT-ROOF: NO G.F.C.I.RECEPTACLE FOR ISLANDS IN KITCHENS. 210.52
RSLV 03/27/2014 03/27/2014 04/17/2014
 
004 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
BSMT-ROOF: LOAD CALCULATIONS REQUIRED FOR PANELS
RSLV 03/27/2014 03/27/2014 04/17/2014
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
BSMT-ROOF: A.F.C.I.BREAKERS NOT PROVIDED THROUGH-OUT
RSLV 03/27/2014 03/27/2014 04/17/2014
 
006 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
BSMT-ROOF: NOT ALL FIXTURES IN BATHROOMS ARE VAPOR PROOF
RSLV 03/27/2014 03/27/2014 04/17/2014
 
007 (999) OTHER
PENTHOUSE: NO G.F.C.I.RECEPTACLE WITHIN 6' OF SINK. 210.8
RSLV 03/27/2014 03/27/2014 04/17/2014
 
008 (999) OTHER
BSMT: NO FLANGE INSTALLED AT END OF TROUGH GOING INTO THE ENDLINEBOX. 376.100
RSLV 03/27/2014 03/27/2014 04/17/2014
 
009 ( 38) MOTOR OVERCURRENT DEVICE DOES NOT HAVE THE PROPER RATING
BSMT: ELEVATOR DISCONNECT IS OVER FUSED MORE THAN 175%. 16.2FLA
RSLV 03/27/2014 03/27/2014 04/17/2014
 
010 (999) OTHER
BSMT: NO G.E.C.FOR TRANSFORMER. 450.10
RSLV 03/27/2014 03/27/2014 04/17/2014
 
011 (999) OTHER
BSMT: SECODARY SIDE OF TRANSFORMER IS OVER FUSED. 240.21(C)(1)
RSLV 03/27/2014 03/27/2014 04/17/2014
 
012 (999) OTHER
BSMT: PRIMARY SIDE OF TRANSFORMER IS OVER FUSED. 240.21(C)(1)
RSLV 03/27/2014 03/27/2014 04/17/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.