BIS Menu  |  Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M332273
Premises: 12 5 AVENUE MANHATTAN BIN: 1009431     Block: 572   Lot: 43
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 12 FIFTH AV Census Tract:   63 Health Area:  5700
BETWEEN 5TH AVENUE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   EAST 8 STREET,    EAST 9 STREET
Status:   C - JOB IS SIGNED OFF 05/11/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/24/2012 3:47 PM
Application Entered:   09/24/2012 Job Start Date:   09/24/2012
Last Change:   05/11/2021 Job End Date:   09/20/2013
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     03/09/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011129 Licensee Name: JESUS M CORPORAN
Firm: 002506 Firm Name: JECO ELEC'L SERVICE CORP.
Firm Phone: 718-542-1931  Firm Address: 1162 INTERVALE AVENUE BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $166.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK HARUNIAN
Owner Business Name: UNITED PRIME
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  21  16               
002  25  10               
003  31  16               
003  32  10               
003  33  16               
004  41  16               
004  42  10               
004  43  16               
004  45  10               
005  51  16               
005  55  10               
006  61  16               
006  62  10               
006  65  10               
007  71  20               
007  72  10               
008  82  10               
008  83  10               
009  91  16               
009  92  10               
009  95  10               
010  103  16               
Buildings Total 87  284  58    86                
Total Units : 515 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 01/17/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APARTMENTS 21, 25, 31, 32, 33, 41, 42, 43, 45, 51, 55, 61, 62, 65, 71, 72, 82, 83, 91, 92, 95, 103

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332273
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/27/2013 12/05/2013 FRI N (5) (0) Y
INSPECTION COMMENTS: NO ACCESS TO APARTMENTS, TENNANTS NOT NOTIFIED
 
(2) 02/19/2014 03/04/2014 DEX Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 03/04/2014 03/12/2014 DNM A (60) (2) Y
INSPECTION COMMENTS: NONE
 
(4) 06/23/2014 07/03/2014 DNM N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW
 
(5) 12/15/2014 12/23/2014 EID N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW = CALLED BY NO ONE SHOWED UP
 
(6) 01/12/2015 01/17/2015 TOR V X (50) (8) Y
INSPECTION COMMENTS: INSPECTED 103,91,92,95,83
 
(7) 03/03/2021 03/03/2021 DWB N (50) (0) Y
INSPECTION COMMENTS: NO SHOW CONTRACTOR HAD WRONG TIME
 
(8) 03/09/2021 03/09/2021 LV1 C R (60) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M332273
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) THROUGHOUT: RECEPTACLES ARE NOT TAMPER PROOR (406.11)
RSLV 03/04/2014 01/12/2015 03/09/2021
 
002 (999) OTHER
(ALL FLOORS)THROUGHOUT: NO A.F.C.I. PROVIDED FOR SMOKE DETECTER (210.12B)
RSLV 03/04/2014 01/12/2015 03/09/2021
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) APT.103: A.F.C.I.NOT PROVIDED(PANEL)
RSLV 01/12/2015 01/12/2015 03/09/2021
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) APT.103: KOS MISSING (PANEL)
RSLV 01/12/2015 01/12/2015 03/09/2021
 
005 (999) OTHER
(ALL FLOORS) APT.91: TR KITCHEN & BATHROOM NOT PROVIDED.. 406.11
RSLV 01/12/2015 01/12/2015 03/09/2021
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) APT.91: A.F.C.I.NOT PROVIDED AC LIVINGROOM
RSLV 01/12/2015 01/12/2015 03/09/2021
 
007 (999) OTHER
(ALL FLOORS)APT.92: TR RECEPTACLE KITCHEN COUNTER NOT PROVIDED.. 406.11
RSLV 01/12/2015 01/12/2015 03/09/2021
 
008 (999) OTHER
(ALL FLOORS)APT.95: TR RECEPTACLE KITCHEN AND BATHROOM NOT PROVIDED. 406.11
RSLV 01/12/2015 01/12/2015 03/09/2021
 
009 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) APT.83: PANEL A.F.C.IS COMBO NOT PROVIDED
RSLV 01/12/2015 01/12/2015 03/09/2021
 
010 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) APT.83: PANEL A.F.C.I.LIVINGROOM AC NOT PROVIDED
RSLV 01/12/2015 01/12/2015 03/09/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back