BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M332163
Premises: 212 WEST 29 STREET MANHATTAN BIN: 1014266     Block: 778   Lot: 47
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 212 W 29 ST Census Tract:   95 Health Area:  5200
BASEMENT, 3RD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 08/10/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/20/2012 4:49 PM
Application Entered:   09/20/2012 Job Start Date:   09/20/2012
Last Change:   08/10/2016 Job End Date:   10/10/2012
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     06/22/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $85.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STACEE KOPATSIS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  3-#8
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/20/2012 Notice: C - CALL TO OFFICE 06/18/2015
Power Issued: 09/20/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332163
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/08/2012 11/18/2012 ARW N (30) (0) Y
INSPECTION COMMENTS: *NO SHOW*
 
(2) 04/02/2015 04/07/2015 EID V G (45) (4) Y
INSPECTION COMMENTS: NEED TO INSP BOTH PNL IN DAPCES ON 3RD FL.NO ACCESS TO BOTH RMS
 
(3) 06/12/2015 06/18/2015 NRS A X E (60) (2) Y
INSPECTION COMMENTS: METER TEMPED
 
(4) 06/22/2016 06/27/2016 BUR C R (25) (0)
INSPECTION COMMENTS: REFER TO M370921 FOR OBJECTION REMOVAL

OBJECTION FOR APPLICATION #: M332163
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BSMT: TAP OFF ON FEEDER COND.TO DISC FOR 2 SPACES(500 TO #3 TO #6)
RSLV 04/02/2015 06/12/2015 06/22/2016
 
002 (999) OTHER
(ALL FLOORS)BSMT: CONDO FEEDING METER DBL UP UNDER SPLIT BOLT.. 110.14(A)
RSLV 04/02/2015 06/12/2015 06/22/2016
 
003 (999) OTHER
(ALL FLOORS) BSMT: NEUTRAL BND AFTER SER.SW.. 250.24(A5)
RSLV 04/02/2015 06/12/2015 06/22/2016
 
004 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(ALL FLOORS)BSMT: COND UNDER #4 RE-IDENTIFIED WITH COLOR TAPE TO METERS.. 210.5
RSLV 04/02/2015 06/12/2015 06/22/2016
 
005 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) 3FL: 5 M/16 SPLICE BOX IN HALL LOOSE FITTINGS
RSLV 06/12/2015 06/12/2015 06/22/2016
 
006 (999) OTHER
(ALL FLOORS) 3FL: NO BRAKER TIE ON MULTIWIRE CIRCUITS 'LSMFT' 2110.4
RSLV 06/12/2015 06/12/2015 06/22/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.