Electrical Application Details for App #: M332005
Premises: 163 WEST 13 STREET MANHATTAN BIN: 1010632     Block: 609   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 175 W 13 ST Census Tract:   71 Health Area:  6100
PIT / MOTOR ROOM Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 08/30/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/17/2012 11:54 AM
Application Entered:   09/17/2012 Job Start Date:   01/07/2013
Last Change:   08/30/2016 Job End Date:   06/07/2013
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011706 Licensee Name: BRIAN FAERBER
Firm: 003598 Firm Name: CENTURY ELECTRIC LLC
Firm Phone: 718-937-6200  Firm Address: 25-25 49TH STREET LONG ISLAND CITY NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $489.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TONY DASILVA
Owner Business Name: CHARLES H. GREENTHAL MGMT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  16
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  250.00
B. Each Additional 10 Floors Or Less  2  166.00
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
EPT                   
ROF        30      40 
Buildings Total        30          40 
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/10/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M332005
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/02/2014 06/10/2014 EDB A (40) (4) Y
INSPECTION COMMENTS: 1P25716,1925715
 
(2) 08/29/2016 08/30/2016 BMP C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M332005
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS)ROOT ELEV RM T-FMR DELTER /WYE CONNECTED DELTA AM 110.2A
RSLV 06/02/2014 06/02/2014 08/29/2016
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS)ROOT ELEV RM #14 AMG FOR CAR LIGHT CKS: 1P25716 AM 210.19 AY
RSLV 06/02/2014 06/02/2014 08/29/2016
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) ROOT ELEV RM EMT NOT PROPERLY SUPPORTED 358.30
RSLV 06/02/2014 06/02/2014 08/29/2016
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) TOP O CAR: GFC5 WORL W/LIGHT 1P25715 AM 110.26
RSLV 06/02/2014 06/02/2014 08/29/2016