Electrical Application Details for App #: M331815
Premises: 55 GREAT JONES STREET MANHATTAN BIN: 1008485     Block: 530   Lot: 32
   
Application Completed and Certified

Filed: 55 GREAT JONES ST Census Tract:   55.02 Health Area:  5700
4TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
Related Job Number:    121177216
DOB Cross Street(s):   LAFAYETTE STREET,    BOWERY
Status:   C - JOB IS SIGNED OFF 09/30/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/11/2012 12:11 PM
Application Entered:   09/11/2012 Job Start Date:   09/11/2012
Last Change:   09/30/2013 Job End Date:   09/10/2013
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     09/16/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $79.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL WITKIN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004    10  40    25  30         
Buildings Total 10  40    25  30              
Total Units : 109 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/15/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M331815
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/26/2012 12/04/2012 JKF N (30) (0) Y
INSPECTION COMMENTS: *CONTRACTOR NOT ON SITE*
 
(2) 05/22/2013 06/10/2013 JKF V (55) (4) Y
INSPECTION COMMENTS: *A/C CONDENSER AND O.C.P.D FOR PANEL FEEDER NOT INSPECTED* **SEE OBJECTIONS
 
(3) 08/13/2013 08/15/2013 IOS A Y (30) (3) Y
INSPECTION COMMENTS: NONE
 
(4) 09/16/2013 09/30/2013 IOS C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M331815
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 58) FIXTURE NOT PROPERLY LOCATED IN CLOTHES CLOSET
CLOSETS
RSLV 05/22/2013 05/22/2013 08/13/2013
 
002 (999) OTHER
PANEL: HANDLE TIES........ - 210.4
RSLV 05/22/2013 08/13/2013 09/16/2013
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
THROUGH-OUT: ALL CHAIN HUNG LIGHT FIXTURES
RSLV 05/22/2013 05/22/2013 08/13/2013
 
004 ( 19) DEFECTIVE WIRING IS IN USE
THROUGH-OUT: PROVIDE A/C UNITS BEING LOW VOLTAGE
RSLV 05/22/2013 05/22/2013 08/13/2013
 
005 (999) OTHER
FLEXIBLE CORD NOT TERMINATED FOR LIGHT IN CLOSET 348.30
RSLV 08/13/2013 08/13/2013 09/16/2013
 
006 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
EMT NOT SUPPORTED IN BASEMENT
RSLV 08/13/2013 08/13/2013 09/16/2013
 
007 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
#2AWG FEEDER NOT IDENTIFIED IN 6X6 SPLICE BOX
RSLV 08/13/2013 08/13/2013 09/16/2013