Electrical Application Details for App #: M331482
Premises: 12 5 AVENUE MANHATTAN BIN: 1009431     Block: 572   Lot: 43
   
Application Completed and Certified

Filed: 12 5 AV Census Tract:   63 Health Area:  5700
FIFTH AVE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   EAST 8 STREET,    EAST 9 STREET
Status:   C - JOB IS SIGNED OFF 03/13/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/31/2012 3:06 PM
Application Entered:   08/31/2012 Job Start Date:   09/03/2012
Last Change:   03/13/2014 Job End Date:   11/30/2012
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     03/04/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011129 Licensee Name: JESUS M CORPORAN
Firm: 002506 Firm Name: JECO ELEC'L SERVICE CORP.
Firm Phone: 718-542-1931  Firm Address: 1162 INTERVALE AVENUE BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $940.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK HARUNIAN
Owner Business Name: UNITED FIFTH LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  36  3 WIRE #6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  4 WIRE #500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 36 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/31/2012 Notice: 1 - FIRST NOTICE 12/05/2013
Power Issued: 08/31/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M331482
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/27/2013 12/05/2013 FRI V E (90) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 02/19/2014 03/04/2014 DEX Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 03/04/2014 03/12/2014 DNM C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M331482
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SVC RM: END LINE BOX- THROUGH NOT MACHANICALLY BONDED, NO FLANGE
RSLV 11/27/2013 11/27/2013 03/04/2014
 
002 ( 19) DEFECTIVE WIRING IS IN USE
SVC RM: #4 CONDUCTORS USED TO TEMP' JUMP-OUT 400A SVC SW
RSLV 11/27/2013 11/27/2013 03/04/2014
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
SVC RM: UNDER SIZE JUMPER. 250.64E, 250.92A3
RSLV 11/27/2013 11/27/2013 03/04/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.