| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
43 |
42 CKT 200 AMP |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)ALL FLS: NO FACE-UP COUNTERTOP RECEPTACLES AS PER ART.406.4E(PANTRY 8,2,10,15,18,32FLS) |
RSLV |
10/21/2013 |
10/21/2013 |
05/26/2022 |
| |
| 002 |
(999) |
OTHER A) 2FL: ALL AREAS MC CABLE BRANCH CKT NOT ALL OUTLET BOXES ARE BOND-ED. 250.146(FITNESS COUNTER) |
OPEN |
10/21/2013 |
10/21/2013 |
|
| |
| 003 |
(999) |
OTHER (ALL FLOORS)B) ALL FLS: ARC FLASH WARNING LABELS ARE MISSING 110.16(NEW PANELS) |
RSLV |
10/21/2013 |
10/21/2013 |
05/26/2022 |
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ALL FLOORS) 10,15FLS: GREENFIELD FOR FURNITURE |
RSLV |
10/21/2013 |
10/21/2013 |
05/26/2022 |
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 002)422.52 ELECTRIC WATER DRINKING FOUNTAIN MISSING GFCIPROTECTION |
OPEN |
04/21/2023 |
04/21/2023 |
|