BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M331397
Premises: 316 MADISON AVENUE MANHATTAN BIN: 1035348     Block: 1277   Lot: 14
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 330 MADISON AV Census Tract:   94 Health Area:  4800
EAST 43RD ST. Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10017 Community Board:   105
Special Place Name:   GUGGENHEIM PARTNERS
DOB Cross Street(s):   EAST 42 STREET,    EAST 43 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/29/2012 2:17 PM
Application Entered:   08/29/2012 Job Start Date:   08/30/2012
Last Change:   08/22/2025 Job End Date:   02/08/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     04/21/2023      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 010905 Licensee Name: SOTIRIOS STATHOPOULOS
Firm: 003195 Firm Name: POLO ELECTRIC CORP. D/B/A
Firm Phone: 212-627-8220  Firm Address: 497 CANAL STREET HELLENIC WIRING CONTRACT NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $3,902.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LORI LOPINTO
Owner Business Name: GUGGENHEIM PARTNERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  43  42 CKT 200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    102  168    62  241             
008    298  728    102  444  35  10  225 
010    298  733    104  444  35  10  225 
015    82  206    106  339  20  195 
018    86  211    104  337  15  180 
032    100  208    62  241  10  45  11  45 
Buildings Total 966  2254    540  2046     115     69     870 
Total Units : 6860 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 04/22/2023
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  OFFICE RENOVATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M331397
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/21/2013 10/31/2013 GYM A (155) (4) Y
INSPECTION COMMENTS: SEE APPLICATION #M325596
 
(2) 05/26/2022 05/26/2022 PHG J Y (50) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED EXCEPT BONDING 2 FLOOR ALL FACE UP OUTLETS AS PER 406 ONLY IN DWELLING UNIT S
 
(3) 04/21/2023 04/22/2023 EDB V X (55) (1)
INSPECTION COMMENTS: (ATOI DAVID RUBINO ) CONTRACTOR REPRESENTATIVE DON'T KNOW LOCATION OF SPLICE BOXES. INSPECTION INCOMPLETE.

OBJECTION FOR APPLICATION #: M331397
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)ALL FLS: NO FACE-UP COUNTERTOP RECEPTACLES AS PER ART.406.4E(PANTRY 8,2,10,15,18,32FLS)
RSLV 10/21/2013 10/21/2013 05/26/2022
 
002 (999) OTHER
A) 2FL: ALL AREAS MC CABLE BRANCH CKT NOT ALL OUTLET BOXES ARE BOND-ED. 250.146(FITNESS COUNTER)
OPEN 10/21/2013 10/21/2013
 
003 (999) OTHER
(ALL FLOORS)B) ALL FLS: ARC FLASH WARNING LABELS ARE MISSING 110.16(NEW PANELS)
RSLV 10/21/2013 10/21/2013 05/26/2022
 
004 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS) 10,15FLS: GREENFIELD FOR FURNITURE
RSLV 10/21/2013 10/21/2013 05/26/2022
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002)422.52 ELECTRIC WATER DRINKING FOUNTAIN MISSING GFCIPROTECTION
OPEN 04/21/2023 04/21/2023



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back