BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M331291
Premises: 155 EAST 26 STREET MANHATTAN BIN: 1018141     Block: 882   Lot: 43
   
Application Completed and Certified

Filed: 155 E 26 ST Census Tract:   68 Health Area:  5300
MOTOR ROOM Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10010 Community Board:   106
DOB Cross Street(s):   BROADWAY ALLEY,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 08/07/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/26/2012 8:59 PM
Application Entered:   08/26/2012 Job Start Date:   10/01/2012
Last Change:   08/07/2013 Job End Date:   10/01/2013
Appointment Status:   
Last Inspection By:   RIVERA, F       On     08/01/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011970 Licensee Name: GUY A FORD
Firm: 004012 Firm Name: ALLIANCE ELEVATOR COMPANY
Firm Phone: 347-592-1555  Firm Address: 36-36 33RD STREET, SUITE 104 LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROD FELDMAN
Owner Business Name: TRI-STAR EQUITIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/29/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MODERNIZATION OF 1 ELEVATOR. N.Y.C. ELEVATOR DEVICE NUMBER 1P 23796.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M331291
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/04/2013 04/12/2013 MFF Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 04/19/2013 04/29/2013 EDB A (30) (3) Y
INSPECTION COMMENTS: *1P27396* **SEE OBJECTIONS
 
(3) 06/19/2013 06/19/2013 FRI J Y (1) (0) Y
INSPECTION COMMENTS: *OBJECTION WRITTEN IN ERROR*
 
(4) 08/01/2013 08/07/2013 FRI C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M331291
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
ROOF: ELEV.CONTROL LIGHT SW FOR CAB LIGHT NO GND.... - 250.4
RSLV 04/19/2013 06/19/2013 08/01/2013
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
ROOF: ELEV.RM EMT NOT SUPPORTED...... - 358.30
RSLV 04/19/2013 06/19/2013 08/01/2013
 
003 (298) DEDICATED AC/HEATING CIRCUIT NOT PROVIDED
ROOF: ELEV.RM.NO A/C RECEPTICAL....... - 620.22B
RSLV 04/19/2013 04/19/2013 06/19/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order