| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
1X200 |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
4X#3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
1X200 |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER 1ST FLR SUB PNL: MULTIWIRE CIR NO GRPED NO SIMULANIOS TRIP 210.4 |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 002 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD 1ST FLR 1,7,EXTENTION CORD USED AS PERMANENT WIRING 400.8 |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 003 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1ST FLR 1,3,2:6 FROM SINK NO GFCI PROTECTION 210.8 |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED 1ST FLR XRAY RM SEALTIDE MORE THANT 6' (NMC) |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 005 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT EMT NOT PROPERLY SUPPORTED (200A PNL) 358.30 |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 006 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT NO GND ROD FOR 200A COMBO SERVICE SWITCH 250.24C |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 007 |
(138) |
METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY BSMT BROKEN CONCENTRIC KNOCKOUT (PNL) 300.10 |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |
| |
| 008 |
(999) |
OTHER 1ST FLR X-RAY DISCONNECT SWITCH DOUBLE LUG (GND)110.14A,3B |
RSLV |
01/17/2013 |
01/17/2013 |
02/14/2013 |