BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M330455
Premises: 145 EAST 73 STREET MANHATTAN BIN: 1043037     Block: 1408   Lot: 20
   
Application Completed and Certified

Filed: 149 E 73 ST Census Tract:   128 Health Area:  4100
APT 3B Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 03/14/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/06/2012 10:01 AM
Application Entered:   08/06/2012 Job Start Date:   08/06/2012
Last Change:   03/14/2013 Job End Date:   12/20/2012
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     03/05/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011760 Licensee Name: MICHAEL HICKEY
Firm: 002949 Firm Name: MWB ELECTRIC CORP.
Firm Phone: 718-418-6921  Firm Address: 64-32 ADMIRAL AVENUE MIDDLE VILLAGE NY 11379 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $139.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: AUDREY CHAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  24 CKT MLO
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3B  28  34    14  28         
Buildings Total 28  34    14  28              
Total Units : 106 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/29/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REWIRE 3 BEDROOMS & 2 BATHROOMS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M330455
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/18/2013 01/29/2013 EDB A (75) (5) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(2) 02/13/2013 02/22/2013 DNM N (20) (0) Y
INSPECTION COMMENTS: *NO ACCESS TO APARTMENT*
 
(3) 03/05/2013 03/14/2013 LBI C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M330455
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
3B: RECEPTACLE BONDED WITH SHORT MOTOR SCREW
RSLV 01/18/2013 01/18/2013 03/05/2013
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
3B: RECEPTACLE NOT PROPERLY GROUNDED/BOUND.... - 250.146
RSLV 01/18/2013 01/18/2013 03/05/2013
 
003 (228) USING PANEL AS A RACEWAY
3B: PANEL USE AS SPLICE BOX....... - 312.8
RSLV 01/18/2013 01/18/2013 03/05/2013
 
004 (999) OTHER
3B: RECEPTACLE MORE THAN 1/4" FROM WALL...... - 314.21
RSLV 01/18/2013 01/18/2013 03/05/2013
 
005 (999) OTHER
3B: EQUIPMENT GROUND CONDUCTOR 20A = #12...... - 250.122
RSLV 01/18/2013 01/18/2013 03/05/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back