Electrical Application Details for App #: M330278
Premises: 1147 2 AVENUE MANHATTAN BIN: 1078347     Block: 1415   Lot: 21
   
Application Completed and Certified

Filed: 1143 SECOND AV Census Tract:   110 Health Area:  4900
LOBBY, COURT YARD, BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):   EAST 60 STREET,    EAST 61 STREET
Status:   C - JOB IS SIGNED OFF 06/22/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/31/2012 11:25 PM
Application Entered:   07/31/2012 Job Start Date:   08/01/2012
Last Change:   06/22/2013 Job End Date:   12/20/2012
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     06/11/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011398 Licensee Name: JOSEPH FERGUSON
Firm: 003192 Firm Name: AVALON ELECTRIC CORP.
Firm Phone: 718-543-2327  Firm Address: 5760 BROADWAY 2ND FLOOR BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $186.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JIM BUSH
Owner Business Name: 1143 SECOND LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200AMP 3/0
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  1 SET OF 3/0
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMP MLO 42CIR
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB    65  10    65  10         
Buildings Total 65  10    65     10           
Total Units : 157 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/31/2012 Notice: 1 - FIRST NOTICE 04/17/2013
Power Issued: 07/31/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REWIRING OF LOBBY LIGHTING AND RECEPTACLES

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M330278
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/08/2013 04/17/2013 TSO A E (35) (5) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 06/11/2013 06/22/2013 JTE C R E (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M330278
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: SERVICE SWITCH AND NO GEC AS PER 250.64
RSLV 04/08/2013 04/08/2013 06/11/2013
 
002 (999) OTHER
BSMT: ILLUMINATION NOT PROVIDED...... - 110.26D
RSLV 04/08/2013 04/08/2013 06/11/2013
 
003 (999) OTHER
OUTSIDE: EGC NOT SUFFICIENT SIZE 30A NEED #10 2 AC UNITS.. - 250.122
RSLV 04/08/2013 04/08/2013 06/11/2013
 
004 (999) OTHER
OUTSIDE: LFMC NOT SUPPORTED 2 AC UNITS..... - 250.30
RSLV 04/08/2013 04/08/2013 06/11/2013
 
005 (999) OTHER
OUTSIDE: NO G.F.C.I.NEAR COMPRESSORS...... - 210.63
RSLV 04/08/2013 04/08/2013 06/11/2013