BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M330272
Premises: 96 EAST 7 STREET MANHATTAN BIN: 1005778     Block: 434   Lot: 12
   
Application Completed and Certified

Filed: 96 E 7 ST Census Tract:   32 Health Area:  6600
ENTIRE Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):    1 AVENUE,    AVENUE A
Status:   C - JOB IS SIGNED OFF 04/09/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/31/2012 8:58 PM
Application Entered:   07/31/2012 Job Start Date:   08/01/2012
Last Change:   04/09/2013 Job End Date:   11/10/2012
Appointment Status:   
Last Inspection By:   KEMPF, JOHN       On     03/28/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012008 Licensee Name: JAROSLAW K KURACH
Firm: 003679 Firm Name: BELMONT ELECTRICAL, INC
Firm Phone: 646-484-6641  Firm Address: 42 WEST 38TH STREET, STE 503 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $135.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NATHARORN GOODMAN
Owner Business Name: SEVEN TURNS REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  3#2 THHN BX
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  20CKT, 120/208THHN
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002                 
003  3,4                 
004  5,6                 
005  7, 8                 
Buildings Total                 24      
Total Units : 31 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 3 - Removed Meters 3 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/31/2012 Notice: 1 - FIRST NOTICE 03/20/2013
Power Issued: 07/31/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELECTRICAL WORK ASSOCIATED WITH INSTALLATION OF NEW ELECTRIC STOVES FOR THE APARTMENTS. SERVICE WORK LIMITED TO INSTALLATION OF 3 NEW METERS IN EXISTING METER BANK. PANELS AND RISERS IN APT 3, 7, 8.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M330272
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/05/2013 03/20/2013 GYM A E (35) (3) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(2) 03/28/2013 04/09/2013 JKF C R E (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M330272
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ALL FLS: ELECT STOVES NEUTRAL BAR BONDED AFTER SERVICE SW- ART.250.24
RSLV 03/05/2013 03/05/2013 03/28/2013
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ALL FLS: 40 AMP ELECT STOVES RECEPTS
RSLV 03/05/2013 03/05/2013 03/28/2013
 
003 (999) OTHER
A) ALL FLS: OUTLET BOXES ARE NOT BONDED..... - ART.250.146(NO BONDING JUMPING PROVIDED)
RSLV 03/05/2013 03/05/2013 03/28/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back