BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M330252
Premises: 431 WEST 37 STREET MANHATTAN BIN: 1088683     Block: 735   Lot: 17
   
Application Completed and Certified

Filed: 431 W 37 ST Census Tract:   111 Health Area:  5500
RESTAURANT Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
Related Job Number:    110220289
DOB Cross Street(s):   DYER AVENUE,    10 AVENUE
Status:   C - JOB IS SIGNED OFF 08/20/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/31/2012 2:02 PM
Application Entered:   07/31/2012 Job Start Date:   08/01/2012
Last Change:   08/20/2015 Job End Date:   08/01/2013
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     06/10/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011735 Licensee Name: YITZHAK ADIKA
Firm: 003323 Firm Name: I.K.E. ELECTRICAL CORP.
Firm Phone: 212-444-2558  Firm Address: 601 WEST 26TH ST.,SUITE 1695 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $875.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: AMNON SHALHOV
Owner Business Name: JOY CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  3-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1-100AMP
C. 3 Phase Up to 225 AMPS  2  2-225AMP 3PHASE
D. 3 Phase Over 225 AMPS  3  3-400AMP 3PHASE
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    90  32    19  90  10         
001    137  42    25  137             
Buildings Total 227  74    44  227     10           
Total Units : 582 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 3
Existing Meters 0 + New Meters 3 - Removed Meters 0 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/31/2012 Notice: C - CALL TO OFFICE 05/07/2015
Power Issued: 07/31/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M330252
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/18/2014 09/24/2014 EDB V E (100) (2) Y
INSPECTION COMMENTS: JOB NOT READY FOR INSPECTION 112713
 
(2) 10/23/2014 10/29/2014 ECH V X G (45) (3) Y
INSPECTION COMMENTS: TEMP POWERNOT REMOVED
 
(3) 05/01/2015 05/07/2015 ECH H X G (30) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 05/21/2015 05/28/2015 GYM J Y E (30) (0) Y
INSPECTION COMMENTS: 400AMP SERVICE SW SHOWING ON DRAWING SEE APPLICATION NO. M367569
 
(5) 06/10/2015 06/16/2015 PHG C R E (40) (0) Y
INSPECTION COMMENTS: WORK REMOVED 400 AMP SERVICE SW. REFER TO APP.#M367569

OBJECTION FOR APPLICATION #: M330252
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR EL RO: NO ARE FLASH WARNING ON NEW EQUIPMENT 110.16
RSLV 09/18/2014 05/21/2015 06/10/2015
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
CELLAR EL RM: OVER 1000 KVA AM 110.2 B,C
RSLV 09/18/2014 05/21/2015 06/10/2015
 
003 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
1ST FL: NEW DISTRIBUTION BOARD 2ND LEVEL GEAR OVER 200A
RSLV 10/23/2014 05/01/2015 05/21/2015
 
004 (999) OTHER
CELLAR,1ST FL: ALL SERVICES MUST BE MARKED. 230.70 AM
RSLV 10/23/2014 05/01/2015 05/21/2015
 
005 (999) OTHER
CELLAR,1ST FL: SERVICES AND PANEL BOARDS MUST BE IDENTIFIED. 230.2(E
RSLV 10/23/2014 05/01/2015 05/21/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order