BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M330053
Premises: 729 BROADWAY MANHATTAN BIN: 1008840     Block: 548   Lot: 70
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 729 BROADWAY Census Tract:   57 Health Area:  5700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Related Job Number:    121088189
DOB Cross Street(s):   WAVERLY PLACE,    ASTOR PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/26/2012 2:19 PM
Application Entered:   07/26/2012 Job Start Date:   07/26/2012
Last Change:   08/22/2025 Job End Date:   01/26/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     10/24/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010346 Licensee Name: PHILIP A ROBINSON
Firm: 001157 Firm Name: PHILIP A. ROBINSON
Firm Phone: 718-783-6542  Firm Address: 43-49 10TH STREET.SUITE 107 LONG ISLAND CITY NY 11101-6999 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $157.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   FOOD DELI TYPE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVE TENEDIOS
Owner Business Name: FRESH & CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  42 AND 30 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  STORE  25  20    10  25             
Buildings Total 25  20    10  25                
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 11/06/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M330053
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/24/2013 11/06/2013 IOS A (40) (4) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M330053
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: 2 600A DISCONNECTS FOR A/CS FED BY 6 AWG CONDUCTORS ARERE-IDENTIFIED WITH TAPE
OPEN 10/24/2013 10/24/2013
 
002 (999) OTHER
MORE THAN ALLOWABLE NUMBER OF CONDUCTORS IN RACEWAY8 16 AWG IN INCH CONDUIT ANNEX C
OPEN 10/24/2013 10/24/2013
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENCLOSURES ON ROOF FOR A/C UNITS NOT BONDED
OPEN 10/24/2013 10/24/2013
 
004 (999) OTHER
NO G.F.C.I.RECEPTACLE ON ROOF FOR A/C UNITS. 210.63
OPEN 10/24/2013 10/24/2013