| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED BASEMENT PANEL(S): COLOR CODE ON GND 210.5 |
RSLV |
06/24/2014 |
10/28/2014 |
04/24/2015 |
| |
| 002 |
(999) |
OTHER BASEMENT PANEL(S) MULTIWIRE CK: NOGROUPED, NO SIMULT TRIP 210.4 |
RSLV |
06/24/2014 |
10/28/2014 |
04/24/2015 |
| |
| 003 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BASEMENT EL. ROM / LAUNDRY ROOM: AC CABLE NOT SECURED 320.30 |
RSLV |
06/24/2014 |
10/28/2014 |
04/24/2015 |
| |
| 004 |
(261) |
ELECTRICAL CLOSETS/SERVICE ROOM IS USED FOR OTHER PURPOSES BASEMENT EL RO USED US LAUNDRY |
RSLV |
06/24/2014 |
10/28/2014 |
04/24/2015 |
| |
| 005 |
( 19) |
DEFECTIVE WIRING IS IN USE BASEMENT ELEV DISC. SW: UNDER SIZE EQIUPMENT GND T.250.122 |
RSLV |
06/24/2014 |
10/28/2014 |
04/24/2015 |
| |
| 006 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED 1 FLOOR NO DISC. MEANS FOR EL HEATER BY ENTER 430.75 |
RSLV |
06/24/2014 |
06/24/2014 |
10/28/2014 |
| |
| 007 |
(186) |
125V, 15/20AMP RECEPTICAL IN MACHINE AREA NOT GFCI BASEMENT NO GFCI RECEPTIOCAL PROVIDED 620.82 |
RSLV |
06/24/2014 |
10/28/2014 |
04/24/2015 |
| |
| 008 |
(999) |
OTHER CELLAR: LIGHT ABOVE ELEVATOR CONTROL IS MELTING. 110.12(B) |
RSLV |
10/28/2014 |
10/28/2014 |
04/24/2015 |
| |
| 009 |
(999) |
OTHER CELLAR: ELEVATOR DISCONNECT GROUND IS NOT CONNECTED IN PANEL250.118 |
RSLV |
10/28/2014 |
10/28/2014 |
04/24/2015 |
| |
| 010 |
(999) |
OTHER 1ST FL: OPEN WIRING TOP OF STAIRCASE. 314.24 |
RSLV |
10/28/2014 |
10/28/2014 |
04/24/2015 |
| |
| 011 |
(999) |
OTHER 1ST FL: A/C UNITS NO EGC THROUGH FMC T-OUT. 250.118(5) |
RSLV |
10/28/2014 |
10/28/2014 |
04/24/2015 |