Premises: 100 BOWERY MANHATTAN BIN: 1003132     Block: 239   Lot: 33
   
Application Completed and Certified

Filed: 100 BOWERY Census Tract:   41 Health Area:  6800
3/FL Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   HESTER STREET,    GRAND STREET
Status:   C - JOB IS SIGNED OFF 07/25/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/13/2012 4:11 PM
Application Entered:   07/13/2012 Job Start Date:   07/13/2012
Last Change:   07/25/2013 Job End Date:   08/30/2012
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     07/02/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $70.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121057300
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MAGNA STAR TUTORING
Authorized Representative:  OLIVER ZHOU
Relationship To Owner:   LEASE HOLDER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    33  50    10  33     
Buildings Total 33  50    10  33            
Total Units : 132 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/30/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M329575
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/20/2013 03/28/2013 IOS A (45) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 04/22/2013 04/30/2013 JKF A Y (40) (2) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(3) 07/02/2013 07/12/2013 IOS C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M329575
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
RECEPTACLES AND SWITCHES NOT PROPERLY BONDED MC CABLE USED 250.146
RSLV 03/20/2013 04/22/2013 07/02/2013
 
002 (999) OTHER
EXTENSION CELLAR NEEDE FOR SWITCHES INROOMS MORE THAN 1/4" DEPTHFROM FACE OF THE SHEETROCK 314.20
RSLV 03/20/2013 03/20/2013 04/22/2013
 
003 (999) OTHER
CIRCUITS NOT GROUPED TOGTHER IN PANEL 210.4(D)
RSLV 03/20/2013 03/20/2013 04/22/2013
 
004 (999) OTHER
INADEQUATE GROUND FROM DISCONNECT ON CONF TO CONDENSER.#10AWG REQINSTEAD OF #12AWG. 250.122
RSLV 03/20/2013 04/22/2013 07/02/2013
 
005 (999) OTHER
ALUMINUM PIPE RUNNING OUTSIDE OF BUILDING TO ROOF NEEDS SUPPORT344.30
RSLV 03/20/2013 04/22/2013 07/02/2013
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
AIR CONDITIONER: AIR CONDITIONER CONDENSER #8/3 CHANGE TO #12 GROUNDALONG PIPE RUN FROM INDOOR BOX
RSLV 04/22/2013 04/22/2013 07/02/2013
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
THROUGH-OUT: MC CABLE BOND ALL JUNCTION AND LIGHTING BOXES
RSLV 04/22/2013 04/22/2013 07/02/2013