BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M329484
Premises: 156 PRINCE STREET MANHATTAN BIN: 1007732     Block: 502   Lot: 20
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 156 PRINCE ST Census Tract:   49 Health Area:  6800
1 ST FLOOR STORE Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Related Job Number:    121129331
DOB Cross Street(s):   WEST BROADWAY,    THOMPSON STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/11/2012 3:53 PM
Application Entered:   07/11/2012 Job Start Date:   07/11/2012
Last Change:   08/22/2025 Job End Date:   12/20/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     05/27/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 011252 Licensee Name: ALBERT V DATTOLO
Firm: 001211 Firm Name: RAINBOW ELECTRIC CO., INC
Firm Phone: 718-521-0926  Firm Address: 76-18 ROCKAWAY BLVD WOODHAVEN NY 11421 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $176.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE MILLER
Owner Business Name: 156 PRINCE ST LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  1 SET 3 WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3 PHASE 100 AMP MAIN LUG
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  ST  10           
Buildings Total 10                
Total Units : 23 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 20 + New Meters 1 - Removed Meters 0 = Total Meters 21

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/11/2012 Notice: 1 - FIRST NOTICE 06/05/2014
Power Issued: 07/11/2012 Response:  

Follow-Up:
Contractor's Comments:  CONVERSION OF APT ON FIRST FLOOR TO STORE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M329484
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/26/2014 03/11/2014 PP1 L (25) (0) Y
INSPECTION COMMENTS: NEED TO KNOW WHAT STORE THIS IS
 
(2) 04/04/2014 04/11/2014 TOR Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 05/27/2014 06/05/2014 IOS V G (25) (3) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M329484
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: NO G.E.C.PROVIDED
OPEN 05/27/2014 05/27/2014
 
002 (999) OTHER
BSMT: NO SUPPLEMENTAL GROUND PROVIDED. 250.53(D)(2)
OPEN 05/27/2014 05/27/2014
 
003 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
BSMT: NEUTRAL NOT BONDED IN SERVICE SWITCH
OPEN 05/27/2014 05/27/2014