BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M329263
Premises: 21 BOND STREET MANHATTAN BIN: 1008427     Block: 529   Lot: 20
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 21 BOND ST Census Tract:   55.02 Health Area:  5700
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   LAFAYETTE STREET,    BOWERY
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/06/2012 10:17 AM
Application Entered:   07/06/2012 Job Start Date:   07/16/2012
Last Change:   08/22/2025 Job End Date:   08/31/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     11/03/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 010410 Licensee Name: MARIO SEGNA
Firm: 001693 Firm Name: SEGNA ELECTRIC INC.
Firm Phone: 718-326-1010  Firm Address: 59-26 57TH STREET MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $235.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 5 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE SOPASAKIS
Owner Business Name: CORNERSTONE MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3 POLE- 600 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  8 - 300 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20- 1 POLE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                       
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 5 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/06/2012 Notice: 1 - FIRST NOTICE 11/12/2014
Power Issued: 07/06/2012 Response:  

Follow-Up:
Contractor's Comments:  REPLACING RUSTED SERVICE EQUIPMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M329263
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/16/2014 07/22/2014 EID N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 07/23/2014 07/29/2014 EID A E (50) (3) Y
INSPECTION COMMENTS: NONE
 
(3) 11/03/2014 11/12/2014 NRS A R G (35) (2) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M329263
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: FIRE ALARM S.S.NO EGC TO WATER PROVIDED. 250.52
RSLV 07/23/2014 07/23/2014 11/03/2014
 
002 (999) OTHER
BSMT: NO DIRECTORY FOR PLP PANEL. 408.4
RSLV 07/23/2014 07/23/2014 11/03/2014
 
003 (999) OTHER
BSMT: DOUBLE LUGGING ON LOAD SIDE OF 4TH FLOOR DISCONNECT. 110.14(A)
RSLV 07/23/2014 07/23/2014 11/03/2014
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
CELLAR: 2 NEW FIRE ALARM SWITCHES. 250.64(E)
OPEN 11/03/2014 11/03/2014
 
005 (999) OTHER
CELLAR: SYSTEM GROUND NOT INSTALLED AS PER 250.64
OPEN 11/03/2014 11/03/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.