BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M329179
Premises: 1035 5 AVENUE MANHATTAN BIN: 1046826     Block: 1496   Lot: 71
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1035 FIFTH AV Census Tract:   150.01 Health Area:  3600
MOTOR ROOM Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 84 STREET,    EAST 85 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/03/2012 9:10 AM
Application Entered:   07/03/2012 Job Start Date:   08/01/2012
Last Change:   08/22/2025 Job End Date:   06/30/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     04/08/2015      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 013229 Licensee Name: MARIO BIANCHI
Firm: 000121 Firm Name: AMER. ELEVATOR & MACH. CO
Firm Phone: 718-784-0101  Firm Address: 36-36 33RD STREET, STE 104 LONG ISLAND CITY NY 11106 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
010030 HOOVER, JOHN R 000121 AMER. ELEVATOR & MACH. CO

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $415.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HARRY SMITH
Owner Business Name: GUMLEY HAFT LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  3  375
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 10/03/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M329179
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/05/2013 08/10/2013 JKF N (15) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 09/20/2013 10/03/2013 EDB A (30) (11) Y
INSPECTION COMMENTS: *#15114,#15113,#15111*
 
(3) 04/08/2015 04/14/2015 LUF N (60) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW

OBJECTION FOR APPLICATION #: M329179
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT: 15114 EMT NOT PROPERLY SUPPORTED(EL.RM).... - 358.30
OPEN 09/20/2013 09/20/2013
 
002 (999) OTHER
BSMT:15114 DISC SW AND CONTROL BOX DOUBLE LUG ON GND... - 110.14A
OPEN 09/20/2013 09/20/2013
 
003 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
BSMT: 15114 TROUGH KO MISSING...... - 110.12A
OPEN 09/20/2013 09/20/2013
 
004 (999) OTHER
BSMT: 15114 PANEL MULTIWIRE CKT NO GROUPED,NO SIMULT TRIP.. - 210.4
OPEN 09/20/2013 09/20/2013
 
005 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
BSMT: 15114 PANEL COLOR CODE ON POWER WIRE...... - 210.5
OPEN 09/20/2013 09/20/2013
 
006 (999) OTHER
BSMT: 15114 PANEL DOUBLE LUG ON POWER (CB)...... - 110.14A,3B
OPEN 09/20/2013 09/20/2013
 
007 (999) OTHER
BSMT: 15113 CONTROLS DOUBLE LUG ON GND..... - 110.14A,3B
OPEN 09/20/2013 09/20/2013
 
008 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT: 15113 EMT NOT PROP.SUPPORTED(ELEV.RM).... - 358.30
OPEN 09/20/2013 09/20/2013
 
009 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT: 15113 CONTROL KO MISSING(ELEV RM)... - 110.12A
OPEN 09/20/2013 09/20/2013
 
010 (999) OTHER
BSMT: 15111 CONTROL DOUBLE LUG ON GND..... - 110.14A,3B
OPEN 09/20/2013 09/20/2013
 
011 (999) OTHER
BSMT: 15111 PANEL (ELEV.RM)MULTIWIRE CKT...... - 210.4
OPEN 09/20/2013 09/20/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.