BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M329055
Premises: 33 WORTH STREET MANHATTAN BIN: 1001963     Block: 176   Lot: 13
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 173 W BROADWAY Census Tract:   33 Health Area:  7700
CELLAR AND APARTMENT Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   WORTH STREET,    LEONARD STREET
Status:   C - JOB IS SIGNED OFF 09/01/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/28/2012 10:18 PM
Application Entered:   06/28/2012 Job Start Date:   07/01/2012
Last Change:   09/01/2017 Job End Date:   12/15/2012
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     07/07/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012158 Licensee Name: HALIM MALAJ
Firm: 004577 Firm Name: HM ELECTRICAL INC
Firm Phone: 718-362-8385  Firm Address: 37-19 55TH STREET WOODSIDE NY 11377 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012158 MALAJ, HALIM 003869 HM ELECTRIC LLC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $441.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: B ROSS
Owner Business Name: MASTER CONTRACTING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    13  13  13             
001    12  12  12             
002    12  12  12             
003    12  12  12             
004    12  12  12             
005    12  12  12             
Buildings Total 73  17  34  73  73                
Total Units : 270 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 4 #10-Wire 0
Existing Meters 6 + New Meters 4 - Removed Meters 6 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/28/2012 Notice: 1 - FIRST NOTICE 06/02/2017
Power Issued: 06/28/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M329055
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/23/2016 12/27/2016 STP V (60) (9)
INSPECTION COMMENTS: FAIL. ALL FEEDERS AND MOTORS NOT FILED FOR.
 
(2) 01/31/2017 01/31/2017 TOR V Y (29) (4)
INSPECTION COMMENTS: FAIL
 
(3) 05/05/2017 05/05/2017 BUR V R (40) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(4) 06/01/2017 06/02/2017 STP V Y (25) (1)
INSPECTION COMMENTS: FAIL.
 
(5) 07/07/2017 07/07/2017 PHG C R (52) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED ENTERED SERVICE ROOM ONLY

OBJECTION FOR APPLICATION #: M329055
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002) 10AWG ON 40AMP CIR BKR 240.4
RSLV 12/23/2016 12/23/2016 05/05/2017
 
002 (999) OTHER
(ALL FLOORS) SHOWER TRIMS NOT WET LOCATION TOUT 410.10
RSLV 12/23/2016 12/23/2016 01/31/2017
 
003 (999) OTHER
(BASEMENT) NO DIRECTORY FOR PANEL 408.4
RSLV 12/23/2016 12/23/2016 01/31/2017
 
004 (999) OTHER
(BASEMENT) GROUND ROD IS CUT 250.52
RSLV 12/23/2016 12/23/2016 01/31/2017
 
005 (999) OTHER
(BASEMENT) 10AWG ON 40AMP CIRCUIT BKR 240.4
RSLV 12/23/2016 12/23/2016 05/05/2017
 
006 (999) OTHER
(BASEMENT) SERVICE ENTRANCE RACEWAY BOND UNDERSIZED 250.102
RSLV 12/23/2016 12/23/2016 05/05/2017
 
007 (999) OTHER
(BASEMENT) 100 AMP CB NO ADDITIONAL FASTENER 408.36
RSLV 12/23/2016 12/23/2016 05/05/2017
 
008 (999) OTHER
(BASEMENT) UPS FLEX CORD EGC NOT CONNECTED 250.118
RSLV 12/23/2016 12/23/2016 05/05/2017
 
009 (999) OTHER
(ROOF) NO IN USE COVER TOUT ROOF 406.8
RSLV 12/23/2016 12/23/2016 01/31/2017
 
010 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) ALL SERVICE EQUIP NOT PROPERLY BONDED
RSLV 01/31/2017 01/31/2017 05/05/2017
 
011 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)FIRE ALARM SERVICE SWICH NOT PROPERLY CONNECTED ( DOUBLE LUGGED ANDWIRE SIZE NOT PROPER ) AT PL SERVICE SWICH .
RSLV 01/31/2017 01/31/2017 05/05/2017
 
012 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) ALL EQUIPMENT NOT PROPERLY FIELD MARKED.
RSLV 01/31/2017 01/31/2017 05/05/2017
 
013 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) FIRE ALARM SERVICE SWICH NOT PROPERLY GROUNDED
RSLV 01/31/2017 01/31/2017 05/05/2017
 
014 (999) OTHER
(CELLAR) FIRE ALARM LINE SIDE CONDUIT NOT BONDED PROPERLY 250.97
RSLV 05/05/2017 05/05/2017 07/07/2017
 
015 (999) OTHER
(CELLAR) LOW VOLTAGE CABLE IN PANEL MIXED WITH LINE VOLTAGE 736.136
RSLV 05/05/2017 05/05/2017 06/01/2017
 
016 (999) OTHER
(CELLAR) FIRE ALARM LINE SIDE CONDUIT NOT SUPPORTED 344.30
RSLV 05/05/2017 05/05/2017 06/01/2017
 
017 (999) OTHER
(BASEMENT) NO SUPP FOR FIRE ALARM SS 250.53
RSLV 06/01/2017 06/01/2017 07/07/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.