| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
2 |
|
| B. 101 Up to 200 AMPS |
2 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 002) 10AWG ON 40AMP CIR BKR 240.4 |
RSLV |
12/23/2016 |
12/23/2016 |
05/05/2017 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) SHOWER TRIMS NOT WET LOCATION TOUT 410.10 |
RSLV |
12/23/2016 |
12/23/2016 |
01/31/2017 |
| |
| 003 |
(999) |
OTHER (BASEMENT) NO DIRECTORY FOR PANEL 408.4 |
RSLV |
12/23/2016 |
12/23/2016 |
01/31/2017 |
| |
| 004 |
(999) |
OTHER (BASEMENT) GROUND ROD IS CUT 250.52 |
RSLV |
12/23/2016 |
12/23/2016 |
01/31/2017 |
| |
| 005 |
(999) |
OTHER (BASEMENT) 10AWG ON 40AMP CIRCUIT BKR 240.4 |
RSLV |
12/23/2016 |
12/23/2016 |
05/05/2017 |
| |
| 006 |
(999) |
OTHER (BASEMENT) SERVICE ENTRANCE RACEWAY BOND UNDERSIZED 250.102 |
RSLV |
12/23/2016 |
12/23/2016 |
05/05/2017 |
| |
| 007 |
(999) |
OTHER (BASEMENT) 100 AMP CB NO ADDITIONAL FASTENER 408.36 |
RSLV |
12/23/2016 |
12/23/2016 |
05/05/2017 |
| |
| 008 |
(999) |
OTHER (BASEMENT) UPS FLEX CORD EGC NOT CONNECTED 250.118 |
RSLV |
12/23/2016 |
12/23/2016 |
05/05/2017 |
| |
| 009 |
(999) |
OTHER (ROOF) NO IN USE COVER TOUT ROOF 406.8 |
RSLV |
12/23/2016 |
12/23/2016 |
01/31/2017 |
| |
| 010 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT) ALL SERVICE EQUIP NOT PROPERLY BONDED |
RSLV |
01/31/2017 |
01/31/2017 |
05/05/2017 |
| |
| 011 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT)FIRE ALARM SERVICE SWICH NOT PROPERLY CONNECTED ( DOUBLE LUGGED ANDWIRE SIZE NOT PROPER ) AT PL SERVICE SWICH . |
RSLV |
01/31/2017 |
01/31/2017 |
05/05/2017 |
| |
| 012 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT) ALL EQUIPMENT NOT PROPERLY FIELD MARKED. |
RSLV |
01/31/2017 |
01/31/2017 |
05/05/2017 |
| |
| 013 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT) FIRE ALARM SERVICE SWICH NOT PROPERLY GROUNDED |
RSLV |
01/31/2017 |
01/31/2017 |
05/05/2017 |
| |
| 014 |
(999) |
OTHER (CELLAR) FIRE ALARM LINE SIDE CONDUIT NOT BONDED PROPERLY 250.97 |
RSLV |
05/05/2017 |
05/05/2017 |
07/07/2017 |
| |
| 015 |
(999) |
OTHER (CELLAR) LOW VOLTAGE CABLE IN PANEL MIXED WITH LINE VOLTAGE 736.136 |
RSLV |
05/05/2017 |
05/05/2017 |
06/01/2017 |
| |
| 016 |
(999) |
OTHER (CELLAR) FIRE ALARM LINE SIDE CONDUIT NOT SUPPORTED 344.30 |
RSLV |
05/05/2017 |
05/05/2017 |
06/01/2017 |
| |
| 017 |
(999) |
OTHER (BASEMENT) NO SUPP FOR FIRE ALARM SS 250.53 |
RSLV |
06/01/2017 |
06/01/2017 |
07/07/2017 |