BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M328807
Premises: 1151 2 AVENUE MANHATTAN BIN: 1078348     Block: 1415   Lot: 21
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1153 2 AV Census Tract:   110 Health Area:  4900
1 FL Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):   EAST 60 STREET,    EAST 61 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/22/2012 1:28 PM
Application Entered:   06/22/2012 Job Start Date:   06/22/2012
Last Change:   08/22/2025 Job End Date:   12/31/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     05/01/2014      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $50.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   OPTIC
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROMEO L DANYAAROV
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20  10    15             
Buildings Total 20  10    15                
Total Units : 50 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 11/19/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M328807
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/13/2013 11/19/2013 PHG V (45) (8) Y
INSPECTION COMMENTS: DID NOT SEE ALL OF THE BASEMENT
 
(2) 05/01/2014 05/15/2014 TOR N (5) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: M328807
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
1ST FL & BSMT: NEUTRAL GROUNDED AFTER SERVICE SWITCHES. 250.28
OPEN 11/13/2013 11/13/2013
 
002 (999) OTHER
1ST FL: NO SIMULTANIOUS TRIP. 210.4
OPEN 11/13/2013 11/13/2013
 
003 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
1FL: RECEPTACLE NOT PROOPERLY GROUNDED. 250.146
OPEN 11/13/2013 11/13/2013
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
1FL BATHROOM: G.F.C.I.HAS NOT BEEN PROVIDED IN BATHROOM
OPEN 11/13/2013 11/13/2013
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
1FL: OUTLET MISSING FINISH PLATE UNDER DESK. 314.25
OPEN 11/13/2013 11/13/2013
 
006 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
STAIRS: BX NOT PROPERLY SECURED. 320.30
OPEN 11/13/2013 11/13/2013
 
007 (999) OTHER
1FL: WIRING METHOD NOT APPROVED. 517.11
OPEN 11/13/2013 11/13/2013
 
008 (999) OTHER
LIGHT SWITCHES IN BATHROOM NOT INSTALLED PROPERLY. 314.15
OPEN 11/13/2013 11/13/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order