BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M328795
Premises: 1031 PARK AVENUE MANHATTAN BIN: 1047948     Block: 1514   Lot: 69
   
Application Completed and Certified

Filed: 1035 PARK AV Census Tract:   148.01 Health Area:  3600
APT 7B Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 85 STREET,    EAST 86 STREET
Status:   C - JOB IS SIGNED OFF 05/28/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/22/2012 10:22 AM
Application Entered:   06/22/2012 Job Start Date:   06/24/2012
Last Change:   05/28/2013 Job End Date:   11/24/2012
Appointment Status:   
Last Inspection By:   ROGALEWSKI, M       On     03/27/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012132 Licensee Name: JOSEPH LENOX, JR
Firm: 003921 Firm Name: COAST 2 COAST ELECTRIC
Firm Phone: 212-684-2659  Firm Address: 32 EAST 31ST STREET, 8TH FL CABLING,INC NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $95.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK MERRIMAN
Owner Business Name: 1035 PARK AVE ASSOC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  SINGLE PHASE 42 CIRCUIT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
007    36  30  15               
Buildings Total 36  30  15                  
Total Units : 82 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/23/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M328795
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/16/2013 01/23/2013 ARW A (60) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 03/27/2013 03/27/2013 MIR C R (1) (0) Y
INSPECTION COMMENTS: *RE:M331945*

OBJECTION FOR APPLICATION #: M328795
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
HATS & NEUTALS NOT GRPED 210.4
RSLV 01/16/2013 01/16/2013 03/27/2013
 
002 (999) OTHER
MULTI WIRE CIRC NOT ON 2POLE 210.4
RSLV 01/16/2013 01/16/2013 03/27/2013
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
BOXES IN DEN NOT COVERED
RSLV 01/16/2013 01/16/2013 03/27/2013
 
004 (999) OTHER
BOXES IN CIMBUSTIBLE MATERIAL NOT FLUISH 314.20
RSLV 01/16/2013 01/16/2013 03/27/2013
 
005 (999) OTHER
BOXES IN KITCHEN NOT 1/4 FORM SURFACE 314.20
RSLV 01/16/2013 01/16/2013 03/27/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back