BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M328551
Premises: 255 WEST 43 STREET MANHATTAN BIN: 1024703     Block: 1015   Lot: 1
   
Application Completed and Certified

Filed: 255 W 43 ST Census Tract:   119 Health Area:  5200
BSMT,1,MEZZ,15TH,ROOF Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10036 Community Board:   105
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 10/09/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/18/2012 3:12 PM
Application Entered:   06/18/2012 Job Start Date:   06/19/2012
Last Change:   10/09/2012 Job End Date:   12/30/2012
Appointment Status:   
Last Inspection By:   SAMARAS TASOS       On     09/26/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010776 Licensee Name: ROBERT E COLOMBO
Firm: 003759 Firm Name: ALLSTATE ELECTRIC CORP
Firm Phone: 212-244-3580  Firm Address: 350 7TH AVENUE, STE. 201 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
7 - HVAC WIRING
Total Fee:  $130.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TIMES SQUARE HOTEL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3P 4W
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  GYM 1            15         
BAS  GYM 2                   
BAS  LAU            25         
BAS  LAU 2                   
001  CEN 1                   
001  CEN 2            15         
001  SEC 1                   
001  SEC2            25         
MZ1  CUCS                   
MZ1  MED R                   
MZ1  MEDRO                   
MZ1  MGNT            25         
MZ1  MGNT1                   
MZ1  SARA                   
015  HALL            15         
015  KITCH                   
015  PENT                   
Buildings Total              173           
Total Units : 173 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/18/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M328551
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/07/2012 08/18/2012 PDI V (40) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 09/26/2012 10/09/2012 TS1 C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M328551
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
MEZZ LEVAL NEW 3 PHASE PNL NO GRDING DETAIL INSTALLED FOR GRD CONDART 250
RSLV 08/07/2012 08/07/2012 09/26/2012
 
002 (999) OTHER
A)MEZZ LEVEL 2-3/4 GREENFIELD FROM PNL TO JUNCTION BOX IN ABOVECEILING, MISSING GRD WIRE IN BOTH ART 250.118(6)
RSLV 08/07/2012 08/07/2012 09/26/2012
 
003 (999) OTHER
B)MEZZ LEVEL CONDUCTORS GOING THRU-BOTH 2-3//4 GREENFIELD ARE #12.DEROTHY OF #10.ART 240.4
RSLV 08/07/2012 08/07/2012 09/26/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.