| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
200 AMPS |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
800 AMPS |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
1 |
400 AMPS |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE GARAGE: SERVICE GFCI NOT WORKING BY CONDENSER UNIT AM. 110.2A |
RSLV |
11/29/2013 |
11/29/2013 |
11/10/2014 |
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED CEL 45 KVA T-FORMER: NOT PROPERLY GND. 250.112 |
OPEN |
11/29/2013 |
11/10/2014 |
|
| |
| 003 |
(999) |
OTHER CEL PANEL AFTER T-FORMER: DOUBLE LUG ON POWER. 110.14A,3B |
OPEN |
11/29/2013 |
11/10/2014 |
|
| |
| 004 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH CEL PANEL AFTER T-FORMER: NEUTRAL BONDED AFTER S.SW 250.24 |
OPEN |
11/29/2013 |
11/10/2014 |
|
| |
| 005 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT EL. RM: SERVICE OVER 1000 KVA. AM.110.2B,C |
OPEN |
11/29/2013 |
11/10/2014 |
|
| |
| 006 |
(999) |
OTHER BSMT 277/480V DISC. SW: CONCENTRIC K/O. 250.97 |
OPEN |
11/29/2013 |
11/10/2014 |
|
| |
| 007 |
(999) |
OTHER BASE: BACK FED MAIN BREAKER NOT SECURED IN LIGHTING SB PANEL408.36D |
OPEN |
11/10/2014 |
11/10/2014 |
|
| |
| 008 |
(999) |
OTHER BASE: NO 480V WARNING. 408.60(C) |
OPEN |
11/10/2014 |
11/10/2014 |
|