BIS Menu  |  Plumb. Inspections  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M327695
Premises: 19 EAST 34 STREET MANHATTAN BIN: 1087934     Block: 864   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 19 E 34 ST Census Tract:   74 Health Area:  5200
SC - 9TH Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 05/10/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2012 10:31 AM
Application Entered:   05/29/2012 Job Start Date:   06/04/2012
Last Change:   05/10/2017 Job End Date:   11/30/2013
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     04/19/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011523 Licensee Name: GLENN J D'ACQUISTO
Firm: 000643 Firm Name: HATZEL AND BUEHLER, INC
Firm Phone: 212-825-1800  Firm Address: 340 MADISON AVENUE NEW YORK NY 10173 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012315 MARI, WILLIAM A 000643 HATZEL AND BUEHLER, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,982.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup: JOANNA PESTKA
Owner Business Name: NY PUBLIC LIBRARY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  3#600
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  3#10, 4#3, 4#8
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  12  4#3/0, 4#4/0
D. Over 250 MCM  8  4#600, 3#350, 3#600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  17  (12)225A, (5)100A
D. 3 Phase Over 225 AMPS  1  1200A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006                      375 
009                      15 
ROF        114         
Buildings Total        114          390 
Total Units : 521 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/08/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB# 5802-2

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M327695
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/25/2014 07/08/2014 JSB A (90) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 04/19/2017 04/20/2017 BMP C R (50) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFICATION.

OBJECTION FOR APPLICATION #: M327695
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) 6 FLOOR 75 KVA TRANS TAP COND OVERFUSED 240.21(C)
RSLV 06/25/2014 06/25/2014 04/19/2017
 
002 (999) OTHER
(ALL FLOORS)6 FLOOR ELECT CLOSET FOR EMER DIST TRANS NOT PROPERLY VENTILATED450.9
RSLV 06/25/2014 06/25/2014 04/19/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.