BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M327078
Premises: 140 ORCHARD STREET MANHATTAN BIN: 1005309     Block: 410   Lot: 11
  Printable (PDF) version of this Permit  

Filed: 85 RIVINGTON ST Census Tract:   18
"MI CASA ES TU CASA" Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   ORCHARD STREET,    LUDLOW STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 05/30/2013
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/11/2012 Job Start Date:   05/07/2012
Last Change:   05/30/2013 Job End Date:   06/10/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   KEMPF, JOHN       On     05/13/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  Y - PARTLY REMOVED

License #: 010708 Licensee Name: JOSEPH DOMINO
Firm: 001928 Firm Name: JOSEPH DOMINO, LIC. ELECT
Firm Phone: 718-592-1086  Firm Address: 45-14 104TH STREET CORONA NY 11368 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $135.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAIRO MORALES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/11/2012 Notice: 1 - FIRST NOTICE 05/30/2013
Power Issued: 05/11/2012 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M327078
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/16/2013 04/24/2013 TSO A E (45) (5) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(2) 05/13/2013 05/30/2013 JKF A Y E (35) (2) Y
INSPECTION COMMENTS: **SEE OBJECTIONS

OBJECTION FOR APPLICATION #: M327078
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: NO LIGHT IN ELECTRICAL ROOM....... - 110.26
RSLV 04/16/2013 04/16/2013 05/13/2013
 
002 (999) OTHER
BSMT: MULTIWIRE BRANCH CIRCUITS NEED HANDLE TIES.... - 210.4
RSLV 04/16/2013 04/16/2013 05/13/2013
 
003 ( 42) BUSHINGS ARE MISSING OR LOOSE
BSMT: BUSHING ON FMC PANEL
RSLV 04/16/2013 04/16/2013 05/13/2013
 
004 (999) OTHER
BSMT: < 6' FMC NEED GROUND . - 250.118
RSLV 04/16/2013 04/16/2013 05/13/2013
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
BSMT: NO PANEL DIRECTORY
OPEN 04/16/2013 05/13/2013
 
006 (999) OTHER
PANEL: GROUNDING.... - 210.4
OPEN 05/13/2013 05/13/2013
 
007 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
PANEL: TO RESTAURANT SPACE
OPEN 05/13/2013 05/13/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.