BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M326399
Premises: 1173 LEXINGTON AVENUE MANHATTAN BIN: 1047510     Block: 1509   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 151 E 80 ST Census Tract:   140 Health Area:  3600
11C, 11D & PHB Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10075 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 10/25/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/25/2012 6:01 PM
Application Entered:   04/25/2012 Job Start Date:   04/25/2012
Last Change:   10/25/2016 Job End Date:   05/20/2013
Appointment Status:   
Last Inspection By:   URIM SYLA       On     10/24/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011829 Licensee Name: VLADIMIR VATA
Firm: 003438 Firm Name: VLASHAVA ELEC CONTR'G COR
Firm Phone: 917-539-7840  Firm Address: 37-08 31ST AVENUE LONG ISLAND CITY NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $193.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PHILIP GOLDFARB
Owner Business Name: GOLDFARB PROPERTIES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011  11C&D  40  42    20  40             
Buildings Total 40  42    20  40                
Total Units : 142 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/25/2012 Notice: 1 - FIRST NOTICE 12/03/2015
Power Issued: 04/25/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  COMBINE THREE APARTMENTS TO DUPLEX APARTMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M326399
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/02/2015 12/03/2015 PHG V E (75) (9) Y
INSPECTION COMMENTS: DID NOT INSPECT OK MOTORS. STRAMERS WIRE SUPPORT FOR 250 MCM
 
(2) 10/24/2016 10/25/2016 UMS C R (50) (0)
INSPECTION COMMENTS: OBJECTIONS CLEARED

OBJECTION FOR APPLICATION #: M326399
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) IMPROPER GFCI PLACEMENT IN BATH ROOM 210.52
RSLV 12/02/2015 12/02/2015 10/24/2016
 
002 (999) OTHER
(ALL FLOORS)IMPROPER RECEPTICLE PLACEMENT IN BOTH LOWER BEDROOMS 210.52
RSLV 12/02/2015 12/02/2015 10/24/2016
 
003 (999) OTHER
(ALL FLOORS) EXPOSED BULB IN MASTER BEDROOM CLOSET 410.16
RSLV 12/02/2015 12/02/2015 10/24/2016
 
004 (999) OTHER
(ALL FLOORS) LIGTHS FIXTURE ABOVE BATH TUB 410.16
RSLV 12/02/2015 12/02/2015 10/24/2016
 
005 (999) OTHER
(ALL FLOORS)KITCHEN UCL FLEX CORD PASSED BEHIND WALL 2 LOCATIONS 400.8
RSLV 12/02/2015 12/02/2015 10/24/2016
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) NO GROUND WHEN CHANGES TO FMC 250 MCM 250.122
RSLV 12/02/2015 12/02/2015 10/24/2016
 
007 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
(ALL FLOORS) A/ STEEMER AIR HANDER NO MOTORS ON APP
RSLV 12/02/2015 12/02/2015 10/24/2016
 
008 (999) OTHER
(ALL FLOORS) NO FIRE STOP PROVIDED IN BASEMENT 300.21
RSLV 12/02/2015 12/02/2015 10/24/2016
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) NO GROUND FOR LIVING ROOM LIGHT FIXTURE 250.122
RSLV 12/02/2015 12/02/2015 10/24/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.