| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
FOUR 42 CIRCUIT PANELS |
| D. 3 Phase Over 225 AMPS |
2 |
TWO 42 CIRCUIT PANELS |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER 1ST FLOOR TWO POLE BREAKERS NO INSTALLED ON MULTI BRANCH CIRCUITSSHUNT PANEL 210.4 B |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |
| |
| 002 |
(999) |
OTHER 1ST FLOOR NEUTRAL AND CIRCUITS NOT GROUPED TOGETHER SHUNT PANEL210.4 D |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |
| |
| 003 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED BASEMENT NEXT TO ELECTRICAL ROOM GFCI NOT BONDED 250.14 |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |
| |
| 004 |
(999) |
OTHER BASEMENT REFRIGERATOR ROOM DISCONNECTS TWO WIRES UNDER THE SAME LUG 110.14(A) |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |
| |
| 005 |
(310) |
SEALTIGHT IS OF EXCESSIVE LENGTH 1ST FLOOR DISHWASHER SEALTIGHT IS MORE THAN 6 FEET 410.10 |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1ST FLOOR KICHEN QUAD OUTLET NOT GFCI 210.8 |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |
| |
| 007 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1ST FLOOR LOFGE AREA OUTLET NOT GFCI 210.8 |
RSLV |
03/14/2013 |
03/14/2013 |
04/22/2013 |