BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M325516
Premises: 509 8 AVENUE MANHATTAN BIN: 1013576     Block: 759   Lot: 45
  Printable (PDF) version of this Permit  

Filed: 519 EIGHTH AV Census Tract:   111 Health Area:  5500
519 Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
DOB Cross Street(s):   WEST 35 STREET,    WEST 36 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 10/21/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/31/2012 12:08 AM
Application Entered:   03/31/2012 Job Start Date:   03/31/2012
Last Change:   10/21/2014 Job End Date:   03/31/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DIAMOND, R.       On     10/15/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011765 Licensee Name: RADOS MILOJKOVIC
Firm: 003122 Firm Name: CENTENNIAL ELEVATOR INDUS
Firm Phone: 718-726-5900  Firm Address: 24-35 47TH STREET ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $790.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHARLES REID
Owner Business Name: KAUFMAN 8TH AVE. ASSOCIAT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  6  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 10/21/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M325516
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/15/2014 10/21/2014 RDI V (75) (6) Y
INSPECTION COMMENTS: COV FOR BMP

OBJECTION FOR APPLICATION #: M325516
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
ELV.RM: #12 COND FUSED AT 200A IN ALL ELEV.DISC.SWITCHES
OPEN 10/15/2014 10/15/2014
 
002 (164) BOXES OR FITTINGS ARE MISSING
ELEV.RM: EMT FITTING MISSING AT ELEV MOTOR
OPEN 10/15/2014 10/15/2014
 
003 (154) THE OVERCURRENT DEVICE HAS NOT BEEN PROPERLY SIZED
ELEV.RM: USE OF LINK FUSE & VARIOUS TYPE FUSES FOR ALL DISC
OPEN 10/15/2014 10/15/2014
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BASE: EMT NOT SUPPORTED PROP BY ELEV.MOTOR
OPEN 10/15/2014 10/15/2014
 
005 ( 19) DEFECTIVE WIRING IS IN USE
ROOF: IMPROPER LB CONDULET USED FOR ELEVBR.CIR.(OPEN END)
OPEN 10/15/2014 10/15/2014
 
006 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
BASE ROOF: KO NOT CLOSED ON ELEV DISC SWITCHES
OPEN 10/15/2014 10/15/2014