BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M325413
Premises: 1463 5 AVENUE MANHATTAN BIN: 1088264     Block: 1745   Lot: 7502
   
Application Completed and Certified

Filed: 1465 FIFTH AV Census Tract:   184 Health Area:  2000
GROUND Admin Area:   M - MANHATTAN Inspection Area:   H
NEW YORK, NY 10035 Community Board:   111
DOB Cross Street(s):   EAST 118 STREET,    EAST 119 STREET
Status:   C - JOB IS SIGNED OFF 11/10/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/29/2012 9:11 AM
Application Entered:   03/29/2012 Job Start Date:   03/29/2012
Last Change:   11/10/2012 Job End Date:   03/29/2013
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     09/17/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012183 Licensee Name: PATRICK J KENNELLY
Firm: 000138 Firm Name: ANTHONY G FERRY INC
Firm Phone: 646-678-3795  Firm Address: 314 CITY ISLAND AVENUE BRONX NY 10464 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $265.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BARRY GURVITCH
Owner Business Name: ARTIMUS CONSTRUCTION
Authorized Representative:  BARRY GURVITCH
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 1 + New Meters 0 - Removed Meters 1 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/29/2012 Notice: 1 - FIRST NOTICE 07/24/2012
Power Issued: 03/29/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M325413
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/28/2012 07/24/2012 JSV A E (60) (5) Y
INSPECTION COMMENTS: COULD NOT INSPECT 200A PANEL, DOOR STUCK CLOSED
 
(2) 09/17/2012 09/24/2012 CLC C R E (90) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M325413
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT SERVICE RACEWAY GROUND UNDER SIZED 450A DISCONNECT(2) ART. 250.24
RSLV 06/28/2012 06/28/2012 09/17/2012
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BASEMENT SUPPLEMENTAL GROUND RACEWAY NOT CONTINOUS
RSLV 06/28/2012 06/28/2012 09/17/2012
 
003 (999) OTHER
BASEMENT LINE & LOAD IN SAME TROUGH (SERVICE) ART 230.7
RSLV 06/28/2012 06/28/2012 09/17/2012
 
004 (999) OTHER
800A DISCONNECT DOOR DOESNT OPEN 90 DEGREE ART.110.26
RSLV 06/28/2012 06/28/2012 09/17/2012
 
005 (999) OTHER
TEMPORARY WIRING STILL CONNECTED TO SERVICE ART 590.3
RSLV 06/28/2012 06/28/2012 09/17/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back