BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M325220
Premises: 201 EAST 10 STREET MANHATTAN BIN: 1006433     Block: 452   Lot: 1
   
Application Completed and Certified

Filed: 160 SECOND AV Census Tract:   40 Health Area:  6200
BASE, GR FL & ROOF Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   EAST 10 STREET,    EAST 11 STREET
Status:   C - JOB IS SIGNED OFF 12/12/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/23/2012 6:03 PM
Application Entered:   03/23/2012 Job Start Date:   03/23/2012
Last Change:   12/12/2012 Job End Date:   03/23/2013
Appointment Status:   
Last Inspection By:   FAY, RICHARD       On     11/19/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $763.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JESSICA SCHUPAK
Owner Business Name: ALTA MAREA GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10  15  10         
GND    50  50  14  50         
ROF    11         
Buildings Total 61  66  19  61     12         
Total Units : 232 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/23/2012 Notice: 1 - FIRST NOTICE 08/18/2012
Power Issued: 03/23/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SPLIT A/C UNITS---WATER HEATER DISH WASHER---REFRIGERATOR--FIRE SUPPRESSION SYSTEM IN KITCHEN---HOOD EXHAUST---KITCHEN EQ

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M325220
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/16/2012 07/31/2012 JTE A E (1000) (2) Y
INSPECTION COMMENTS: NO ACCESS TO WATER GRD RM NEED TO INSPECT ISLATED GRD FOR 200AMP PNL GRD BAR
 
(2) 08/03/2012 08/18/2012 JSB A R E (45) (1) Y
INSPECTION COMMENTS: NONE
 
(3) 11/19/2012 11/24/2012 RFY C R E (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M325220
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 52) TEMPORARY OPEN WIRING FEEDS OTHER FLOORS
THRUOUT NO GFCI PROVIDED FOR BATHRMS THRUOUT
RSLV 07/16/2012 07/16/2012 08/03/2012
 
002 (999) OTHER
BSMT SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE ART 250.28
RSLV 07/16/2012 07/16/2012 08/03/2012
 
003 (999) OTHER
BSMT,SVC ENT LINE AND LOAD IN SAME RACEWAY 230.7
RSLV 08/03/2012 08/03/2012 11/19/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order