BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M325022
Premises: 145 EAST 73 STREET MANHATTAN BIN: 1043037     Block: 1408   Lot: 20
   
Application Completed and Certified

Filed: 149 E 73 ST Census Tract:   128 Health Area:  4100
3A Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 04/04/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/19/2012 9:49 PM
Application Entered:   03/19/2012 Job Start Date:   03/20/2012
Last Change:   04/04/2013 Job End Date:   12/15/2012
Appointment Status:   
Last Inspection By:   KAFFETZAKIS, MICHAIL       On     02/27/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011903 Licensee Name: WIESLAW MAKSIM
Firm: 003541 Firm Name: DENMAR ELECTRIC CORP
Firm Phone: 718-533-6753  Firm Address: 5 PENN PLAZA 19TH FLOOR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $129.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH LASPINA
Authorized Representative:  JOSEPH LASPINA
Relationship To Owner:   ASSISTANT SEC.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3A  44  76  48  44         
Buildings Total 44  76  48  44              
Total Units : 217 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/07/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M325022
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/30/2013 02/07/2013 EDB A (60) (7) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(2) 01/31/2013 02/08/2013 MFF N (30) (0) Y
INSPECTION COMMENTS: *NO SHOW*
 
(3) 02/27/2013 03/05/2013 MFF C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M325022
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (340) RECEPTACLES NOT TAMPERPROOF
3A: WALL RECEPTACLE NOT TAMPER PROOF....... - 406.11
RSLV 01/30/2013 01/30/2013 02/27/2013
 
002 (340) RECEPTACLES NOT TAMPERPROOF
3A: MASTER BEDROOM RECEPTACLE NOT TAMPER PROOF..... - 406.11
RSLV 01/30/2013 01/30/2013 02/27/2013
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
3A: ALL UTILITY (A/H) CLOSET NOT ON A.F.C.I.(LIGHT)... - 210.12B
RSLV 01/30/2013 01/30/2013 02/27/2013
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
3A: A.F.C.I.COMBINATION NOT PROVIDED...... - 210.12B
RSLV 01/30/2013 01/30/2013 02/27/2013
 
005 (999) OTHER
3A: PANEL MULTIWIRE CKT NO GROUPED NO SIMULTANIOUS TRIP... - 210.4
RSLV 01/30/2013 01/30/2013 02/27/2013
 
006 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
3A: PANEL NEUTRAL BONDED AFTER SER SW..... - 250.24A5
RSLV 01/30/2013 01/30/2013 02/27/2013
 
007 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
3A: NO PANEL DIRECTORY........ - 408.4
RSLV 01/30/2013 01/30/2013 02/27/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order