| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(340) |
RECEPTACLES NOT TAMPERPROOF 3A: WALL RECEPTACLE NOT TAMPER PROOF....... - 406.11 |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |
| |
| 002 |
(340) |
RECEPTACLES NOT TAMPERPROOF 3A: MASTER BEDROOM RECEPTACLE NOT TAMPER PROOF..... - 406.11 |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 3A: ALL UTILITY (A/H) CLOSET NOT ON A.F.C.I.(LIGHT)... - 210.12B |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 3A: A.F.C.I.COMBINATION NOT PROVIDED...... - 210.12B |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |
| |
| 005 |
(999) |
OTHER 3A: PANEL MULTIWIRE CKT NO GROUPED NO SIMULTANIOUS TRIP... - 210.4 |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |
| |
| 006 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH 3A: PANEL NEUTRAL BONDED AFTER SER SW..... - 250.24A5 |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |
| |
| 007 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 3A: NO PANEL DIRECTORY........ - 408.4 |
RSLV |
01/30/2013 |
01/30/2013 |
02/27/2013 |