Electrical Application Details for App #: M324187
Premises: 101 EAST 68 STREET MANHATTAN BIN: 1081419     Block: 1403   Lot: 1
   
Application Completed and Certified

Filed: 695 PARK AV Census Tract:   120 Health Area:  4100
7TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10065 Community Board:   108
Special Place Name:   CUNY HUNTER COLLEGE
DOB Cross Street(s):   EAST 68 STREET,    EAST 69 STREET
Status:   C - JOB IS SIGNED OFF 07/25/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/28/2012 4:50 PM
Application Entered:   02/28/2012 Job Start Date:   02/28/2012
Last Change:   07/25/2015 Job End Date:   02/28/2013
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     07/17/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011643 Licensee Name: MARK W BOBB
Firm: 003203 Firm Name: BOBTEK ELECTRICAL CORP.
Firm Phone: 718-763-2563  Firm Address: 934 EAST 51ST STREET BROOKLYN NY 11203 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $175.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: C.D.E. AIR CONDITIONING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 01/15/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CHILLER UPGRADE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M324187
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/30/2014 10/07/2014 EDB V (50) (4) Y
INSPECTION COMMENTS: APPLICATION FILED INCORRECTLY CONTRACTOR HAS 2 CHILLER AND MORE RISER
 
(2) 01/06/2015 01/15/2015 EID V X (50) (1) Y
INSPECTION COMMENTS: INSPECTED ALL EQUIPMENT IN BSMT AND 1ST FL FEEDER & EQUIPMENT AND ROOF. CONT. MUST REFILE DESC TO REFLECT TOTAL SCOPE OF WORK
 
(3) 01/30/2015 02/04/2015 TOR N (20) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR,NO SHOW
 
(4) 03/01/2015 04/07/2015 LUF N (40) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(5) 04/10/2015 04/14/2015 EDB J Y (60) (0) Y
INSPECTION COMMENTS: NO UPDATE APPLICATION
 
(6) 07/09/2015 07/09/2015 HMC J Y (1) (0) Y
INSPECTION COMMENTS: NONE
 
(7) 07/17/2015 07/25/2015 LUF C R (30) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: M324187
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
CELLAR: EL.RM.OVER 1000 KVA,CONTRACTOR ADD KRP-C - 800 SP IN S.SAM.110.2B,C. SERVICE A 4000A 277/480V
RSLV 09/30/2014 04/10/2015 07/09/2015
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
CELLAR: EL.RM. 100A A/C DISC SM #6 AWG FUSED AT 80A. T.310.16
RSLV 09/30/2014 07/09/2015 07/17/2015
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
CELLAR: EL.RM.UNDERSIZE EQUIPMENT GND FOR 80A. T.250.122
RSLV 09/30/2014 07/09/2015 07/17/2015
 
004 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
CELLAR: UNDERSIZE TAP CONDUCTOR FOR A/C - 1 FROM CH-2. 240.21
RSLV 09/30/2014 01/06/2015 04/10/2015
 
005 (999) OTHER
EL RM: ALL EQUIPMENT NOT LABELLED IN CELLAR 230.2E
RSLV 01/06/2015 01/06/2015 04/10/2015