Electrical Application Details for App #: M323956
Premises: 27 MORTON STREET MANHATTAN BIN: 1009934     Block: 587   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 271/2 MORTON ST Census Tract:   67 Health Area:  6400
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):    7 AVENUE SOUTH,    BEDFORD STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/21/2012 5:01 PM
Application Entered:   02/21/2012 Job Start Date:   02/21/2012
Last Change:   08/22/2025 Job End Date:   03/20/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     11/04/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011749 Licensee Name: JEROME DALY
Firm: 003344 Firm Name: AMRA ELECTRICAL CORP
Firm Phone: 718-444-5209  Firm Address: 1415 UTICA AVENUE BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $154.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: LMF-RS CONTRACTING INC
Authorized Representative:  RENATA SPORCIC
Relationship To Owner:   REPRESENTIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  2X36CKT PANELS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  000    20    10  30         
Buildings Total   20    10  30              
Total Units : 68 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 11/13/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M323956
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/04/2013 11/13/2013 NRS A (40) (7) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M323956
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (115) GFCI HAS NOT BEEN PROVIDED FOR KITCHEN RECEPTACLES
GROUND FL: KITCHEN RECEPTACLES ARE NON GFCI. 210.8(B)(2)
OPEN 11/04/2013 11/04/2013
 
002 (999) OTHER
GROUND FL: NO TIE BREAKERS PROVIDED IN BOTH PANELS FOR MULTIWIRECIRCUITS. 210.4(B)
OPEN 11/04/2013 11/04/2013
 
003 (999) OTHER
GROUND: NO BUSHING PROVIDED FOR FEEDER IN RIGHT HAND SIDE PANEL300.4(G)
OPEN 11/04/2013 11/04/2013
 
004 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
BACKYARD: A/C DISCONNECTS NOT GROUNDED, NO GR LUG
OPEN 11/04/2013 11/04/2013
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
GROUND BRANCH CIRCUITS NOT IDENTIFIED IN BOOTH PANELS
OPEN 11/04/2013 11/04/2013
 
006 (219) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:RMC)
BACKYARD: VERTICAL ROCC RUN TO A/C DISONNECTS NOT PROPERLYSUPPORTED
OPEN 11/04/2013 11/04/2013
 
007 (999) OTHER
BACKYARD: RMC CONDUIT BODY (T) FASTENED TO A/C DISCONNECT USING EMTSETSCREV CONNECTOR. 300.15
OPEN 11/04/2013 11/04/2013