BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M323528
Premises: 19 EAST 34 STREET MANHATTAN BIN: 1087934     Block: 864   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 19 E 34 ST Census Tract:   74 Health Area:  5200
CELLAR - 9TH FL. Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 05/10/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/08/2012 3:37 PM
Application Entered:   02/08/2012 Job Start Date:   02/15/2012
Last Change:   05/10/2017 Job End Date:   02/28/2013
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     04/19/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011523 Licensee Name: GLENN J D'ACQUISTO
Firm: 000643 Firm Name: HATZEL AND BUEHLER, INC
Firm Phone: 212-825-1800  Firm Address: 340 MADISON AVENUE NEW YORK NY 10173 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012315 MARI, WILLIAM A 000643 HATZEL AND BUEHLER, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,767.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup:
Owner Business Name: THE NY PUBLIC LIBRARY
Authorized Representative:  JOANNE PESTKA
Relationship To Owner:   SR. VP CAPITAL PLANNING


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1200A
E. Over 1200 AMPS  1  2500A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  15  6SETS 4#600, 9SETS 3#600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF              20         
Buildings Total              20           
Total Units : 20 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/08/2012 Notice: 1 - FIRST NOTICE 07/08/2014
Power Issued: 02/08/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB # 5802

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M323528
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/25/2014 07/08/2014 JSB A E (180) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 04/19/2017 04/20/2017 BMP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M323528
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BASEMENT GROUND ELECT COND NOT PROPERLY TERMNATED 250.64
RSLV 06/25/2014 06/25/2014 04/19/2017
 
002 (999) OTHER
(ALL FLOORS) BASEMENT PANIC BARS NOT PROVIDED 110.26
RSLV 06/25/2014 06/25/2014 04/19/2017
 
003 (999) OTHER
(ALL FLOORS)BASEMENT 1600 SELT OF NEW WORK NOT AS PER LAYOUT 110.2B
RSLV 06/25/2014 06/25/2014 04/19/2017
 
004 (999) OTHER
(ALL FLOORS)BASEMENT SUPP GROUND ELECTRODE NOT POVIDED 250.53 (D) (2)
RSLV 06/25/2014 06/25/2014 04/19/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.