| BUILDING OVERVIEW |
Are Feeders Being Installed? : |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE NO APPLICATION ON FILE FOR BASEMENT 2 - 200AMP SVC SWS,BASEMENTPANEL,BRANCH CKTS |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT: SVC HND CONDUCTOR NOT INSTALLED |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 003 |
(999) |
OTHER BSMT: BOTH 200AMP SVC SWS NEUTRAL NOT BONDED..... - 250.28 |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 004 |
(999) |
OTHER BSMT: BOTH 200AMP SVC SWS BONDING UNDER SIZE...... - 250.66 |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 005 |
(999) |
OTHER BSMT: SVC ENT RACEWAY NOT BONDED...... - 250.92 |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 006 |
(999) |
OTHER BSMT: 4 - WIRE METER NEUTRAL BONDED AFTER SVC SW..... - 250.24A5 |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 007 |
( 29) |
OUTLET BOXES ARE NOT COVERED BSMT: SVC AREA MISSING COVERS THROUGH-OUT |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 008 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX BSMT: KO MISSING THROUGH-OUT |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 009 |
(999) |
OTHER BSMT: DEFECTIVE EQUIPMENT IN USE SVC RUSTY...... - 110.3 |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 010 |
(999) |
OTHER BSMT: END LINE BOX MORE THAN 2 CONDUCTORS UNDER ONE BUG NUT.... -110.14 |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 011 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE BSMT: 12 WIRE FUSED AT 30AMPS 6 WIRE FUSED AT 100AMP |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 012 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT: EMT NOT SUPPORTED CEILING |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 013 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT: BX CABLES NOT SUPPORTED |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 014 |
( 19) |
DEFECTIVE WIRING IS IN USE BSMT: DEFECTIVE WIRING CONDUCTORS SPLICE NOT IN A BOX |
OPEN |
01/18/2012 |
01/18/2012 |
|
| |
| 015 |
(999) |
OTHER BSMT: BX CABLES AND 1900 BOXES RUSTY..... - 110.14 |
OPEN |
01/18/2012 |
01/18/2012 |
|