Electrical Application Details for App #: M323039
Premises: 1529 YORK AVENUE MANHATTAN BIN: 1050371     Block: 1560   Lot: 28
   

DOB NOW: Inspections


Filed: 1531 YORK AV Census Tract:   136 Health Area:  3800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):    1 AVENUE,    YORK AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   01/26/2012 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     01/18/2012      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: GENERAL PROPERTY MGMT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/26/2012
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 01/26/2012
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M323039
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/18/2012 01/26/2012 CLC W (75) (15)
INSPECTION COMMENTS: SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: M323039
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
NO APPLICATION ON FILE FOR BASEMENT 2 - 200AMP SVC SWS,BASEMENTPANEL,BRANCH CKTS
OPEN 01/18/2012 01/18/2012
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: SVC HND CONDUCTOR NOT INSTALLED
OPEN 01/18/2012 01/18/2012
 
003 (999) OTHER
BSMT: BOTH 200AMP SVC SWS NEUTRAL NOT BONDED..... - 250.28
OPEN 01/18/2012 01/18/2012
 
004 (999) OTHER
BSMT: BOTH 200AMP SVC SWS BONDING UNDER SIZE...... - 250.66
OPEN 01/18/2012 01/18/2012
 
005 (999) OTHER
BSMT: SVC ENT RACEWAY NOT BONDED...... - 250.92
OPEN 01/18/2012 01/18/2012
 
006 (999) OTHER
BSMT: 4 - WIRE METER NEUTRAL BONDED AFTER SVC SW..... - 250.24A5
OPEN 01/18/2012 01/18/2012
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT: SVC AREA MISSING COVERS THROUGH-OUT
OPEN 01/18/2012 01/18/2012
 
008 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT: KO MISSING THROUGH-OUT
OPEN 01/18/2012 01/18/2012
 
009 (999) OTHER
BSMT: DEFECTIVE EQUIPMENT IN USE SVC RUSTY...... - 110.3
OPEN 01/18/2012 01/18/2012
 
010 (999) OTHER
BSMT: END LINE BOX MORE THAN 2 CONDUCTORS UNDER ONE BUG NUT.... -110.14
OPEN 01/18/2012 01/18/2012
 
011 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT: 12 WIRE FUSED AT 30AMPS 6 WIRE FUSED AT 100AMP
OPEN 01/18/2012 01/18/2012
 
012 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT: EMT NOT SUPPORTED CEILING
OPEN 01/18/2012 01/18/2012
 
013 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT: BX CABLES NOT SUPPORTED
OPEN 01/18/2012 01/18/2012
 
014 ( 19) DEFECTIVE WIRING IS IN USE
BSMT: DEFECTIVE WIRING CONDUCTORS SPLICE NOT IN A BOX
OPEN 01/18/2012 01/18/2012
 
015 (999) OTHER
BSMT: BX CABLES AND 1900 BOXES RUSTY..... - 110.14
OPEN 01/18/2012 01/18/2012