Electrical Application Details for App #: M323012
Premises: 164 EAST 87 STREET MANHATTAN BIN: 1087120     Block: 1515   Lot: 45
  Printable (PDF) version of this Permit  

Filed: 164 E 87 ST Census Tract:   148.02 Health Area:  3600
BASTMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   P - OBJECTN PENDING AT CONTRACTOR 03/08/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/25/2012 10:29 AM
Application Entered:   01/25/2012 Job Start Date:   01/25/2012
Last Change:   03/08/2013 Job End Date:   01/25/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     02/28/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010939 Licensee Name: MICHAEL L ALPHONSE
Firm: 002249 Firm Name: BESTCO GENERAL ELEC. MAIN
Firm Phone: 718-324-5582  Firm Address: 922 EAST 233RD STREET BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $190.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: HAI ADVISORS LLC.
Authorized Representative:  HAI ADVISORS
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600AMP. 3-PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3- 2/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/08/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALL 1-600AMP.3-PHASE S/SWITCH FOR FIRE PUMP

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M323012
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/02/2012 05/10/2012 GYM A (40) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/28/2013 03/08/2013 LBI A Y (30) (4) Y
INSPECTION COMMENTS: *SEE OBJECTIONS

OBJECTION FOR APPLICATION #: M323012
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: FIRE PUMP SERVICE SWITCH IS NOT ON LINE SIDE OF SERVICEART.695.4B - 230.82
RSLV 05/02/2012 05/02/2012 02/28/2013
 
002 (999) OTHER
A) BSMT: FIRE PUMP SERVICE SWITCH NOT MARKED..... - 695.4B
OPEN 05/02/2012 02/28/2013
 
003 (999) OTHER
B) BSMT: FUSE NOT MARKED 600 AMP FIRE PUMP DISCONNECT.. - ART.240.83
OPEN 05/02/2012 02/28/2013
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT: RACEWAY ON LINE SIDE OF SVC NOT BONDED PER 250.92(A)
OPEN 02/28/2013 02/28/2013
 
005 (137) GROUNDING ELECTRODE CONDUCTOR IS NOT OF PROPER SIZE FOR SERVICE
BSMT: GROUND ELECTRODE COND RAN FOR FIRE PUMP SVC UNDERSIZED FOR 2/0SERVICE ENT....... - TABLE 250.66
OPEN 02/28/2013 02/28/2013
 
006 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
BSMT: MAIN BONDING JUMPER FOR FIRE PUMP SERVICE..... - 250.24(B),250.28
OPEN 02/28/2013 02/28/2013
 
007 (999) OTHER
BSMT: FIRE PUMP GROUND ELCTRODE CONDUCTOR RACEWAY NOT CONTINIOUS- 250.64(E)
OPEN 02/28/2013 02/28/2013