Electrical Application Details for App #: M323006
Premises: 62 WEST 11 STREET MANHATTAN BIN: 1009514     Block: 574   Lot: 11
   
Application Completed and Certified

Filed: 62 W 11 ST Census Tract:   63 Health Area:  5700
APT. 2R Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 01/29/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/25/2012 9:24 AM
Application Entered:   01/25/2012 Job Start Date:   01/25/2012
Last Change:   01/29/2013 Job End Date:   01/25/2013
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     01/16/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010939 Licensee Name: MICHAEL L ALPHONSE
Firm: 002249 Firm Name: BESTCO GENERAL ELEC. MAIN
Firm Phone: 718-324-5582  Firm Address: 922 EAST 233RD STREET BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $56.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELICIA LING
Authorized Representative:  ELICIA LING
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ1                 
Buildings Total                 
Total Units : 16 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/11/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 1-100AMP.208 VOLT 24CKT.PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M323006
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/26/2012 05/04/2012 CLC A (30) (1) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 11/29/2012 12/11/2012 EDB A R (60) (4) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(3) 01/16/2013 01/25/2013 TSO C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M323006
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
APT.2R: TAMPER PROOF DEVICE NOT USED THROUGH-OUT APARTMENT. - 406.11
RSLV 04/26/2012 04/26/2012 11/29/2012
 
002 (340) RECEPTACLES NOT TAMPERPROOF
BEDROOM: A/C RECEPTACLE NOT TAMPER PROOF... - 406.11
RSLV 11/29/2012 11/29/2012 01/16/2013
 
003 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
LIV/DIN RM: NO A/C RECEPTACLE PROVIDED FOR LIV/DINING ROOM.... -210.52(1)
RSLV 11/29/2012 11/29/2012 01/16/2013
 
004 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
2R: COLOR CODE FOR #12 AWG FOR EQUIPMENT GND..... - 210.5
RSLV 11/29/2012 11/29/2012 01/16/2013
 
005 (999) OTHER
2R: MULTIWIRE CKTS NO GROUPED NO SIMULTANIOUS TRIP... - 210.4
RSLV 11/29/2012 11/29/2012 01/16/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order