Electrical Application Details for App #: M322459
Premises: 930 LEXINGTON AVENUE MANHATTAN BIN: 1081418     Block: 1403   Lot: 1
   
Application Completed and Certified

Filed: 930 LEXINGTON AV Census Tract:   120 Health Area:  4100
ROOMS 507, 512, 514, 5C02 & 5T Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10065 Community Board:   108
Special Place Name:   5TH FL. AUTISM CENTER RENO.
DOB Cross Street(s):   EAST 68 STREET,    EAST 69 STREET
Status:   C - JOB IS SIGNED OFF 04/03/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/10/2012 12:43 PM
Application Entered:   01/10/2012 Job Start Date:   01/10/2012
Last Change:   04/03/2013 Job End Date:   02/10/2012
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     12/19/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011879 Licensee Name: BERNARD FARSKY
Firm: 003499 Firm Name: OFF SHORE ELECTRIC CORP
Firm Phone: 212-290-2200  Firm Address: 135-31 KEW GARDENS ROAD RICHMOND HILL NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $277.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT LEMIEUX
Owner Business Name: CUNY DEPT. DESIGN CONST
Authorized Representative:  ROBERT LEMIEUX
Relationship To Owner:   EXEC. DIRECTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  4 #4/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1 100A & 1 225 A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  5C02                 
005  507    15    10  25     
005  512    17    13         
005  514    21    10         
Buildings Total   53    19  35     28         
Total Units : 139 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/30/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M322459
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/11/2012 07/30/2012 LBI V (60) (5) Y
INSPECTION COMMENTS: *HOT WATER HEATERS NOT ACCESSIBLE AT TIME OF INSPECTION* SEE VIOLATION DETAILS
 
(2) 12/19/2012 01/04/2013 LBI C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M322459
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
5FL: ROMEX TEMP NOT REMOVE3D FROM CEILING(ENTIRE)...... - 590.3(D)
RSLV 07/11/2012 07/11/2012 12/19/2012
 
002 (999) OTHER
5FL: 200A BREAKER SUPPLYING 100A RATED PANEL(PANEL LRP.5)408.36(B)
RSLV 07/11/2012 07/11/2012 12/19/2012
 
003 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
ROOF: #3 AWG FEEDING ROOF AC UNIT
RSLV 07/11/2012 07/11/2012 12/19/2012
 
004 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
5FL: PANEL LRP.5(ENTIRE)
RSLV 07/11/2012 07/11/2012 12/19/2012
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
5FL: JUNCTION BOXES MISSING COVERS(ENTIRE)
RSLV 07/11/2012 07/11/2012 12/19/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.